Accessory Parts; Installation Of R410 Air Conditioner - Toshiba MMY-MAP0726FT2P-UL Installation Manual

Hide thumbs Also See for MMY-MAP0726FT2P-UL:
Table of Contents

Advertisement

Available languages

Available languages

2

Accessory parts

Q'ty
Part name
MAP072 MAP096 MAP120 MAP144 MAP168
Owner's Manual
1
1
1
Installation Manual
1
1
1
Attached pipe
(Ø7/8" both forward
1
1
and downward)
Attached pipe
(Ø1 1/8" both forward
1
and downward)
Attached pipe
(Ø3/4" both forward
1
and downward)
Attached pipe
(Ø3/4" both forward
1
1
and downward)
Attached pipe
(Ø7/8" both forward
and downward)
Attached pipe
(Ø1/2" for draw-out
1
1
1
forward)
Attached pipe
(Ø1/2" for draw-out
1
1
1
downward)
Attached pipe
(Ø5/8" for draw-out
forward)
Attached pipe
(Ø5/8" for draw-out
downward)
Attached pipe
(Ø3/4" for draw-out
forward)
Attached pipe
(Ø3/4" for draw-out
downward)
5-EN
1122001201_EN FR.indd 3
1122001201_EN FR.indd 3
Shape
Usage
(Be sure to hand it to the
1
1
customers.)
1
1
This manual for installer.
Suction-side gas pipe
Ø1"→Ø7/8" pipe fitting
Suction-side gas pipe
1
1
Ø1"→Ø1 1/8" pipe fitting
Discharge-side gas pipe
Ø5/8"→Ø3/4" pipe fitting
* Flare the connector on the
outdoor unit for installation.
Discharge-side gas pipe
* Flare the connector on the
outdoor unit for installation.
Discharge-side gas pipe
Ø3/4"→Ø7/8" pipe fitting
1
1
* Flare the connector on the
outdoor unit for installation.
Liquid pipe
* Flare the connector on the
outdoor unit for installation.
1
Liquid pipe
* Flare the connector on the
outdoor unit for installation.
1
1
Liquid pipe
Ø5/8"→Ø3/4" pipe fitting
* Flare the connector on the
outdoor unit for installation.
1
– 3 –
3

Installation of R410 air conditioner

This air conditioner adopts the HFC refrigerant (R410A) which does not deplete the ozone layer.
• To prevent mixing of refrigerant or refrigerating oil, the size of the charge port of the main unit or connecting
section of the installation tool differs to that of an air conditioner for the former refrigerant.
Accordingly, exclusive tools are required for the new refrigerant (R410A) as shown below.
• For connecting pipes, use new and clean piping materials so that water or dust does not enter.
■ Required Tools and Cautions on handling
Prepare the tools and equipment listed in the following table before starting the installation work.
: R410A exclusive
: Generic
Tools/equipment
Manifold gauge*
Vacuuming/charging refrigerant
and operation check
Charging hose
Gas leak detector
Gas leak check
Vacuum pump with backflow
Vacuum drying
prevention function
Flare tool
Flare machining of pipes
Bender
Bending pipes
Refrigerant recovery equipment
Refrigerant recovery
Torque wrench
Tightening flare nuts
Pipe cutter
Cutting pipes
Brazing torch and nitrogen
Braze pipes
cylinder
Refrigerant charging scales
Charging refrigerant
4 mm hexagon wrench
Opening liquid valve
Use
Usable if dimensions are adjusted.
Ø1/2" (12.7 mm) and Ø5/8" (15.9 mm)
6-EN
9/2/16 1:30 PM
9/2/16 1:30 PM

Advertisement