Installation Of The Outdoor Unit - Toshiba MMY-MAP0726FT2P-UL Installation Manual

Hide thumbs Also See for MMY-MAP0726FT2P-UL:
Table of Contents

Advertisement

Available languages

Available languages

6

Installation of the outdoor unit

WARNING
Install the outdoor unit securely in a location where the base can sustain the weight adequately.
If strength is insufficient, the unit may fall down resulting in human injury.
CAUTION
Drain water is discharged from the outdoor unit. (Especially while heating)
Install the outdoor unit in a place with good drainage.
For installation, be careful of the strength and level of the foundation so that abnormal sounds (vibration or noise)
are not generated.
REQUIREMENT
Installation in a snowfall area
1. Install the outdoor unit on a higher foundation than the snowfall or set up a stand to install the unit so that snowfall
will not affect the unit.
• Set up a stand higher than the snowfall.
• Apply an angled structure to the stand so that drainage will not be prevented. (Avoid using a stand with a fl at
surface.)
2. Mount a snowfall-hood onto the air inlet and the air outlet.
• Leave enough space for the snowfall-hood so that it will not be an obstacle for the air inlet and the air outlet.
1. To install multiple outdoor units, arrange them with 7.9" (200mm) (recommendation, at least 0.8" (20mm)) or more
spaces in between.
Fix each outdoor unit with M12 anchor bolts at 4 positions. 0.8" (20mm) projection is appropriate for an anchor bolt.
L
L
Recommendation 7.9" (200mm), at least 0.8" (20mm) or more.
11-EN
1122001201_EN FR.indd 6
1122001201_EN FR.indd 6
Snowfall-hood for air
outlet (locally procured)
Snowfall-hood for air
outlet
(4 faces)
(locally procured)
Stand
(locally procured)
Unit: in (mm)
M12 anchor bolt
4 positions/unit
• Anchor bolt positions are as shown below:
Continuous hole
(0.6" × 0.8" (15 × 20)
long hole)
Model type
A
MAP0726
27.6" (700)
2. To draw out the refrigerant pipe from the underside,
set the height of the stand to 19.7" (500mm) or more.
4. If vibration-proof rubbers (including vibration-proof blocks) are used, fit them under the whole clamping legs.
Correct
Install the vibration-proof
Anchor bolt
rubber so that the bend part
Vibration-proof rubber
of the fi xing leg is
grounded.
Incorrect
The bend part of the
fi xing leg is not
grounded.
5. Be careful of the connecting arrangement of the header unit and follower units. Set the outdoor units in order of
capacity from the one with the largest capacity. (A (Header unit) ≥ B ≥ C)
• Be sure to use a header unit for the leading outdoor unit to be connected to the main pipe. (Figure 1, 3 and 6)
• Be sure to use a T-shaped branch joint (RBM-BT14FUL: separately purchased) to connect each outdoor unit.
• Be careful of the direction of the outdoor unit connection piping kit for the liquid side. (As shown in Figure 2, an
outdoor unit connection piping kit cannot be attached so that the refrigerant of the main pipe fl ows directly into
the header unit.)
– 6 –
A
L+11.4" (290)
A
B
L
B
B
L
Recommendation 7.9" (200),
39.0" (990)
at least 0.8" (20) or more
3. Do not use 4 stands on the corner to support the
outdoor unit.
Incorrect
Correct
Correct
Incorrect
Incorrect
EN
FR
12-EN
9/2/16 1:30 PM
9/2/16 1:30 PM

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents