■ Resetting to factory default address
Method 1
Follow steps 1 through 11 by using a direct wired remote control (page 22) to reset line (system) address, indoor
unit addresses and group addresses to "0099".
Method 2
Clearing all the indoor unit addresses on a single refrigerant line and reset all addresses to the factory default
settings follow the steps below:
1. To turn off the refrigerant line and reset all address to the factory default settings follow the steps below:
A. On the header outdoor unit, open the connector between (U1, U2) and (U3, U4) terminals.
B. On the header outdoor, interface PC board, SW30 DIP switch 2, set to ON.
Header
Follower unit
unit
U3 U4
U3 U4
U1 U2
U5 U6
U1 U2
U5 U6
U1 U2
U1 U2
A B
A B
Remote
Remote
control
control
Indoor units to have their addresses initialized
1
Turn on the indoor and outdoor units of the refrigerant line for which initialize the addresses to
be initialized. About one minute after turning on the power, confi rm that the 7-segment display
on the header outdoor unit indicates "U.1. - - -" and operate the interface P.C. board on the
header outdoor unit of the refrigerant line as follows:
SW01
SW02
SW03
Confirm that the 7-segment display indicates
2
1
2
"A.d.buS" and turn SW04 ON for more than five
seconds.
Confirm that the 7-segment display indicates
2
2
2
"A.d.nEt" and turn SW04 ON for more than five
seconds.
2
Confi rm that the 7-segment display indicates "A.d. c.L." and set SW01, SW02 and SW03 to 1, 1, 1
respectively.
3
After a time "U.1.L08" appears on the 7-segment display if the address clearing has been
completed successfully.
4
Set the addresses again after fi nishing the clearance.
49-EN
1122001201_EN FR.indd 25
1122001201_EN FR.indd 25
Central control
Header
Header
Follower unit
unit
unit
U3 U4
U3 U4
U3 U4
U1 U2
U5 U6
U1 U2
U5 U6
U1 U2
U5 U6
U1 U2
U1 U2
U1 U2
A B
A B
A B
Remote
Remote
control
control
SW04
Clearable addresses
System/indoor unit/group address
Central control address
– 25 –
■ Setting when connecting
indoor units to FS (Flow
Selector) unit
◆ Cautions to connection of indoor
unit
• When connecting the indoor units to a single port
type FS unit and a branch of the multi port type FS
unit, it is necessary to set up the CODE No..
Be sure to set up the CODE No. after setup of
address.
• When connecting the indoor units to a single port
type FS unit and a branch of the multi port type FS
unit, it is possible to connect with multiple groups
U1
U2
and connect individually.
U3
U4
Single port type FS unit
Control wiring
between indoor
Remote control
unit and FS unit
(Within 49 ft
(15 m))
Group control
Multi port type FS unit
Remote control
Group control
Piping
Single port type FS unit
Control wiring
between indoor
unit and FS unit
Remote control
Group control
◆ How to set up CODE No. [ 0E ]
It is necessary to set up in case of the group control.
.
2
5
1
Push and hold the
the same time for more than 4 seconds.
Piping
is displayed in the UNIT No. window.
In this time, the fans of all the indoor units in the
group control start the fan operation.
Indoor unit
2
Using the set temperature buttons
, select the CODE No. "
3
Change SET DATA to "
buttons
/
.
4
Push
button.
5
Push
button. Then the setup fi nished.
Piping
◆ How to set up CODE No. [ 14 ]
It is necessary to set up group address in case of the
Indoor unit
group control.
0 : Individual
1 : Header unit
2 : Follower unit
Single port type FS unit
◆ How to set up CODE No. [ FE ]
In cases other than connecting with one indoor unit or
Piping
one group in one branching, it is necessary to set up.
• As for both single port type and multi port type,
set up CODE No. "FE" in one branching within the
range of 1~64.
Indoor unit
This CODE No. should not be duplicate in one
system.
Incorrect
◆ How to set up CODE No. [ FD ]
In cases other than connecting with one indoor unit or
one group in one branching, it is necessary to set up.
0 : Heating prioritized (Factory default)
1 : Cooling prioritized
3
4
1
,
, and
buttons at
/
".
" by the timer
50-EN
9/2/16 1:30 PM
9/2/16 1:30 PM