January 2017
Table 5-1 Status LEDs, Display messages, and current loop
Current
State
output
Calibrate sensor
3.0 mA
Normal operation
4.0 mA
Start-up delay
3.0 mA
(90 seconds)
Access main
3.0 mA
menu & options
Memory error
2.5 mA
Sensor lead open
2.5 mA
Excess drift
2.5 mA
(>10%)
Auto Zero set
3.0 mA
Apply cal. gas
3.3 mA
Span is set,
3.6 mA
remove gas
Calibration
3.6 mA
successful
Sensor guard
20.0 mA
Gas present
> 4–20 mA
Failed calibration
3.0/3.3 mA
14
Status LED
Display
red or green
N/A
N/A
Green
N/A
00 %LEL
blip/blink
Red slow
N/A
Start delay
flash
Switch on
N/A
(10→0)
Red slow
Memory
N/A
flash
error
Red slow
N/A
Sensor Fault
flash
Red
N/A
Neg. drift
blip/blink
Green
Apply clean
N/A
Solid
air
Red fast
Apply 50%
N/A
flash
span gas
Green
N/A
Remove gas
solid
Green
Cal.
N/A
solid
complete
Red Solid
N/A
100% LEL
Red
1–100% full
N/A
blip/blink
scale
Red
Green
Fail cal.
flash
flash
Table 5-2 RTU Status register (40002) Read only (binary)
RTU Status registers and meaning
RTUstat_fault
RTUstat_low_alarm
RTUstat_high_alarm
RTUstat_low_alarm_latched
RTUstat_high_alarm_latched
RTUstat_lel_60_latched
RTUstat_lel_100_latched
RTUstat_powerUp
RTUstat_cal_cycle
RTUstat_zeroing
RTUstat_apply_span_gas
RTUstat_calibrating
RTUstat_remove_gas
RTUstat_cal_complete
RTUstat_mem_error
1.
Register 40001 = LEL output (read only)
2.
Register 40002 = RTU status (read only)
3.
Register 40101 = Reset latched relays (write)
Operations Manual
FGD-MAN-0047
0x0001
Fault(sensor)
0X0002
Low alarm tripped
0X0004
High alarm tripped
0X0008
Low alarm latched
0X0010
High alarm latched
0X0020
60% LEL latched
0x0040
100% LEL latched
0x0080
Power up delay
Calibration cycle in
0X0100
progress
0x0200
zeroing
0x0400
Apply span gas
0x0800
Calibrating
0x1000
Remove gas
0x2000
Calibration complete
0X4000
Memory error