Maintenance; Remove The Outlet Front Grille; Open Inlet Faceplate; Opening Inspection Hatch - Lindab Plexus Installation Instructions Manual

Active chilled beam
Hide thumbs Also See for Plexus:
Table of Contents

Advertisement

Installation instruction

7. Maintenance

The interval of cleaning depends on the indoor environment where the beam is placed. Under optimal conditions the beams
only need cleaning every 5 years.
Open the inlet plate using no tools (7.2)
Clean the battery downside and the inlet faceplate inner parts with a dust cleaner / vacuum cleaner.
Only use lukewarm water and a mild detergent and a piece of wet cloth to clean the inlet face plate.
Open the inspection hatch (7.3)
Clean the air plenum chamber and air connection with a vacuum cleaner
Lower battery if water pipe connections are connected to system by flexhoses. ( Otherwise this is not possible, See 7.4).
Clean the top side of the battery, nozzle plate, JetCones and the mixing chamber with a dust cleaner / vacuum

7.1 Remove the outlet front grille

Not relevant for Plexus.

7.2 Open inlet faceplate

Service wires
Lindab reserves the right to make changes without prior notice
2021-03-02
l in d a b | w e s i m p l i f y c o n s t r u c tio n

7.3 Opening inspection hatch

Plexus
cleaner.
33