5. Troubleshooting

5.1 Fault finding chart

WARNING!
Before removing the terminal box cover, make sure that the electrical supply has been switched off
and that it cannot be accidentally switched on.
The pumped liquid may be scalding hot and under high pressure. Before any removal or dismantling
of the pump, the system must be drained or the isolation valves on both sides of the pump must be
closed.
Fault
1. The pump does not
run.
None of the indicator
lights are on.
2. The pump does not
run.
The green indicator
light is on.
3. Three-phase
pumps only:
The pump is run-
ning.
The red and green
indicator lights are
on.
4. Noise in the system.
The green indicator
light is on.
5. Noise in the pump.
The green indicator
light is on.
6. Insufficient heat in
some places in the
heating system.
Cause
a) One fuse in the installation
is blown.
b) External circuit breaker is
switched off.
c) Current-/voltage-operated
ground fault interrupter has
tripped.
d) The pump's internal thermal
overload switch has cut out
(standard module only).
a) Rotor blocked, but the
pump hasn't been cut out
by the thermal overload
switch.
b) The speed switch module
has not been fitted.
a) The pump is running with
the wrong direction of
rotation.
a) Air in the system.
b) The pump flow is too high.
c) The pressure is too high.
a) Air in the pump.
b) The inlet pressure is too
low.
a) The pump performance is
too low.
Remedy
Replace the fuse.
Switch the circuit breaker on.
Repair the insulation defects and reset the
interrupter.
Check that the liquid temperature falls within the
specified range.
With external on/off changeover contact:
The pump will restart automatically when it has
cooled to normal temperature.
With external on/off impulse contacts:
The pump can be restarted when it has cooled to
normal temperature.
Switch off the electrical supply and clean/repair
the pump.
Switch off the electrical supply at the external
circuit breaker and fit the speed switch module
into position.
Switch off the electrical supply at the external
circuit breaker and interchange any two phases
(leads) in the pump terminal box.
Vent the system.
Reduce the pump performance.
Reduce the pump performance.
Vent the pump.
Increase the inlet pressure and/or check the air
volume in the expansion tank (if installed).
Increase the pump performance, if possible, or
replace the pump with a pump with higher flow.