CIAT BOX TRI Eco+ User Manual page 29

Electronic controller
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 19
No.
Description
Temperature setpoint in
p
p
frost protection mode
16
Temperature sensor
calibration:
To correct sensor
measurements
17
Min. WINTER voltage,
terminal 11 (0 10V):
terminal 11 (0-10V):
Minimum coil water
supply setting
18
Max. WINTER voltage,
terminal 11 (0-10V):
terminal 11 (0-10V):
Maximum coil water
supply setting
19
Min. SUMMER voltage,
terminal 11 (0-10V):
l 11 (0 10V)
t
i
Minimum coil water
supply setting
20
Max. SUMMER voltage, Unit
terminal 11 (0-10V):
Maximum coil water
supply setting
21
Unit
°C
Min.
Min
5
5
Max.
15
Default
8
Increment
0.5
Unit
°C
Min.
Mi
-5
5
Max.
5
Default
0
Increment
0.2
Unit
V
Min.
0
Max.
Setting 19
Default
0
Increment
0.2
Unit
V
Min.
Setting 18
Max.
10
Default
10
Increment
0.2
Unit
V
Min.
0
Max.
Setting 21
Default
0
Increment
0.2
V
Min.
Setting 20
Max.
10
Default
10
Increment
0.2
12
Possible choices
5 to 15 C
5 to 15°C
In SUMMER mode, frost protection mode is turned off
and converted to ECO mode.
Terminal 11 is used to control a (0-10V) valve
actuator (supplied in optional valve kit).
WINTER Min. setting: in WINTER mode in full fresh
air use, it is recommended to always supply the heat
exchanger with water so as to prevent it from freezing
(min. setting > 0V)
Max. setting: when air heaters are selected based on
M
tti
h
i h
the minimum air mixing rate, the total heat output
delivered is often greater than the building's heat
requirements. This excess output can be reduced by
limiting the maximum voltage delivered by these
terminals (max. setting <10 V)
-
(
)
t
l
t d b
d

Advertisement

Table of Contents
loading

Table of Contents