Example of the AC fuse cooling

The AC fuses must be cooled by forced cooling. If the fuses are not located in the same
cubicle with the supply/rectifier module, the module cooling fan does not supply the cooling
air for the fuses but you must use a separate cooling fan.
The following figures show an example of the cooling system using a thermal switch for the
air temperature monitoring near the AC fuses.
2
MAIN SUPPLY
SUPPLY
DISCONN. SWITCH
=-Q1
=-F1.1
;1L1
1
2
1
2
=-F1.2
;1L2
3
4
1
2
=-F1.3
;1L3
5
6
1
2
13
14
;1PE:1
050/10D
DEFAULT INPUT DESIGNATION
DI1...DI6; NOMINAL VOLTAGE 24VDC
-DI1
TEMP FAULT_01
-DI2
RUN ENABLE_01
-DI3
MCB FEEDBACK_01
-DI4
CIRCUIT BRK FAULT_01
-DI5
EARTH FAULT_01
-DI6
RESET_01
Note: The connection of temperature monitoring requires proper insulation between busbars and thermal
switch.
1
TEMPERATURE MONITORING
MAIN
CONTACTOR
=-Q2
1
2
=-F6
3
4
1
2
5
6
020/13D
Part of ZCU-14 shown from sheet 050
14
13
14
13
14
13
14
14
11
12
24
21
22
Cabinet construction 35
Description
1
Thermal switch
2
Cooling fan
;F6:2
9E
;X22:35
050/13A
;XDI:1
001/9E
;X21:30
13A
;X22:1
020/6E
13
;Q24:4
020/10C
14
11
12
10
DSU MODULE
=-T01
-X1.1
1
2
~
-X7
1
2
3
4
5
6
7
8