3Com 4210 Getting Started page 30

Switch 4210 series
Hide thumbs Also See for 4210:
Table of Contents

Advertisement

30
C
2: I
HAPTER
NSTALLING THE
Connecting the Switch
to the Redundant Power
System
S
WITCH
1500W rectifiers can provide up to 4500W. Hot removal or insertion of a rectifier
does not affect the -48V DC output voltage.
Table 14 shows an example of the total power available from several 1500W
rectifiers.
A minimum of two rectifiers are required for each shelf to provide N+1 rectifier
redundancy.
Table 14 Power Availability
1
No Rectifier
1500W
Redundancy
N+1 Rectifier
-
Redundancy
The unearthed -48V DC power distribution provides the mechanism to connect to
the Switch 4210. The distribution consists of several circuit breakers and
connection terminals for the positive (common) and negative -48V outputs.
Individually connect each Switch 4210 to a circuit breaker terminal.
You can also connect a battery to battery terminals prior to the DC power
distribution to provide uninterrupted power and to be protected against the loss
of AC mains power.
3Com's RPS solution uses -48V DC power distribution. The RPS system provides
bulk -48V DC power that is separately distributed to a number of network
switches.
Each RPS consists of a shelf that can house from one to six rectifiers, a Distribution
Module, and a Management Module.
When connecting the RPS to the switch, the circuit breaker and 2-core cables need
to be matched to the switch's power rating. Table 15 shows the recommended
circuit breaker and cable rating for the Switch 4210. The recommended cable
length should not exceed three metres (9.84 feet).
Table 15 Switch 4210 Circuit Breaker and Cable Ratings
PoE
WARNING: Make sure to follow the RPS Manufacturers recommendations when
connecting the cable to the RPS.
WARNING: Ensure that the circuit breaker in the RPS is in the open (off) position
when connecting the cable to the RPS and the cable and connector to the switch.
WARNING: Ensure that the positive terminal on the switch is connected to the
positive (common) terminal of the RPS and that the negative terminal on the
switch is connected to the negative (circuit breaker) terminal of the RPS.
Rectifiers
2
3
3000W
4500W
1500W
3000W
Circuit Breaker Minimum 2-Core Cable Diameter
25A C type
12 AWG (solid or stranded cable
4
5
6
6000W
7500W
9000W
4500W
6000W
7500W
)