Heavy-duty fan-forced ceiling-mount heater

Advertisement

If you will use an external temperature control (external thermostat) to control the
heater to be operated or not, please follow below attention points:
1. Make sure that the heater's temperature control knob (thermostat knob) is turned fully
clockwise.
2. Connect the wire according to below wiring diagram.
Circuit diagram
Figure 10
3. The external temperature control (external thermostat) must be in accordance with the
requirement of UL or ETL standard.
4. The current carrying capacity of external temperature control can not less than 26.5A.
5. The lead wire of external temperature control (external thermostat) can not less than
10AWG.