For all Deringer Series Valves
Important Installation
Information Read before
installing
WARNING
!
WARNING: Make sure to thoroughly flush out water lines prior to installation of a Deringer. If water lines are NOT thoroughly flushed, debris will damage the check and
relief valves and will not be covered under warranty.
For Deringer Models 20/20X/30/30X/40/40X/50/50X
Install with FLEX Couplings or Flange Adapters Only.
DO NOT use RIGID Couplings or Groove Reducing
Couplings!
For Deringer Models 30/30X/30G/30GX/50/50X/50G/50GX
Micro Bypass Orientation
Please follow these instructions to properly orient the
meters on the Deringer 30 & 50 micro bypass assemblies:
1. The Deringer water
meters are rotated 90
degrees during shipping
to protect the plastic
register from damage.
For additional detailed maintenance and repair instructions,
including videos, visit BackflowDirect.com/downloads.html
2. Using an adjustable
wrench loosen the meter
couplings on both sides
of the meter and rotate
the meter into the proper
orientation.
WA R N I N G
!
WARNING
!
You are required to consult the local building and plumbing
codes prior to installation. If the information in this manual
is not consistent with local building or plumbing codes,
the local codes should be followed. Inquire with governing
authorities for additional local requirements.
Flange
Adapters
3. Using an adjustable
wrench tighten the meter
couplings on both sides
of the meter (proper
meter orientation).
UserGuide-A-Deringer
Read this manual BEFORE using this equipment.
Failure to read and follow all safety and use information can
result in death, serious personal injury, property damage, or
damage to the equipment.
Keep this manual for future reference.
FLEX
RIGID
Groove Reducing
Couplings
Couplings
FLOW
Couplings

Advertisement

loading

Summary of Contents for Watts AMES Deringer Series

  • Page 1 UserGuide-A-Deringer User Guide Deringer ™ WA R N I N G For all Deringer Series Valves Read this manual BEFORE using this equipment. Failure to read and follow all safety and use information can result in death, serious personal injury, property damage, or damage to the equipment.
  • Page 2 Tighten both bolts. to the sensing line body relief valve. Apply a small coupler. coating of lubricant to O-Ring. For additional detailed maintenance and repair instructions, including videos, visit BackflowDirect.com/downloads.html UserGuide-A-Deringer 2018 © 2020 Watts...
  • Page 3 NFPA 72 and the auxiliary switch per NAPA 70 (NEC). Remember to cap off any unused wire and that your conduit connections are water tight. For additional detailed maintenance and repair instructions, including videos, visit BackflowDirect.com/downloads.html UserGuide-A-Deringer 2018 © 2020 Watts...
  • Page 4 USA: Backflow T: (978) 689-6066 • F: (978) 975-8350 • AmesFireWater.com USA: Control Valves T: (713) 943-0688 • F: (713) 944-9445 • AmesFireWater.com Canada: T: (888) 208-8927 • F: (888) 479-2887 • AmesFireWater.ca Latin America: T: (52) 55-4122-0138 • AmesFireWater.com UserGuide-A-Deringer 2018 EDP# 2916025 © 2020 Watts...