ABB K-Line Plus KP-8 Installation & Maintenance Instructions Manual page 7

Low voltage power circuit breaker
Table of Contents

Advertisement

IB 6.2.11.1-1C
Page 7
Figure 2 - Electrical Characteristics of Control Devices
Nominal Control
Voltage
120VAC (60 Hz)
240VAC (60 Hz)
48VDC
125VDC
250VDC
* Approximate steady state values; momentary in-rush currents are approximately 6-8 times these values
located in the lower-rear portion of EO circuit breakers,
and controls the electrical closing functions of the
breaker.
The "anti-pump" feature of the SSCD
prevents a second electrical closing until the first
closing signal is released. For example, if the breaker
is closed electrically and the signal is maintained, the
SSCD will not permit the breaker to be closed
electrically again after a trip until the electrical close
signal is released.
Shunt Trip - The shunt trip is standard on EO breakers
and optional on MO breakers.
releases the stored energy of the opening springs
causing the circuit breaker to open.
Closing Spring Charging Motor - When the motor
disconnect switch is ON, the charging motor is
energized automatically by internal limit switches to
charge the closing springs electrically.
Closing Spring Check Switch (CSCS) - The CSCS
automatically disconnects the power to the charging
motor when the closing springs are fully charged.
Integral Auxiliary Switch - The integral circuit breaker
mounted auxiliary switch is standard on EO breakers
and MO breakers with shunt trip, and optional on MO
breakers without shunt trip. The standard configuration
contains the four "a" and four "b" contacts (with three
"a" and two "b" contacts available for customer use via
the
secondary
disconnects).
mechanically interconnected with the circuit breaker
mechanism such that, with the circuit breaker closed,
the "a" contacts are closed and the "b" contacts are
open. With the circuit breaker open, the "a" and "b"
contacts reverse positions. This switch is located in the
lower left portion of the circuit breaker.
Optionally, EO breakers and MO breakers with shunt
Average
Shunt Trip or
Charging
Close Coil
Motor
Current
Current*
10A
6.5A
5A
1.2A
25A
3.1A
10A
1.3A
5A
0.7A
When energized, it
The
switch
is
Closing
Shunt Trip
Circuit
Circuit
Voltage
Voltage
Range
Range
104-127
104-127
208-254
208-254
38-56
28-56
100-140
70-140
200-280
140-280
trip can be fitted with a 16-pole switch, which offers an
additional four each "a" and "b" contacts for customer
use.
Undervoltage Trip Device (Optional) - The electrically
reset undervoltage trip device (UVD) is a single-phase
device which automatically trips the circuit breaker
when the line voltage decreases to 30 to 60 percent of
the rated voltage.
This device is presently only
available for instantaneous trip operation.
undervoltage trip device is an integral unit which may
be added to the circuit breaker either at the factory or in
the field.
When the breaker is tripped by the UVD, the Automatic
Trip Indicator will extend through the front plate of the
breaker escutcheon.
until the UVD is electrically reset by the control power.
See Figure 3 for electrical characteristics of the UVD.
Figure 3 - Undervoltage Trip Device
Operating Data
Current at
Service Voltage
Rated
Voltage
120VAC (60 Hz)
0.5A
240VAC (60 Hz)
0.2A
480VAC (60 Hz)
0.1A
48VDC
0.3A
125VDC
0.2A
250VDC
0.1A
ABB
Recommended
Control Fuse Size
10A
10A
15A
10A
10A
The indicator cannot be reset
Maximum
Dropout
Pickup
Voltage
Voltage
Range
102
36-72
204
72-144
408
144-288
41
15-29
106
38-75
212
75-150
The