ABB K-Line Plus KP-8 Installation & Maintenance Instructions Manual page 12

Low voltage power circuit breaker
Table of Contents

Advertisement

ABB
K-Line Plus Secondary Disconnect Assignments
Pin
Description
A1
Charge Motor +
A2
Shunt Trip -
A3
Close Coil +
A4
Shunt Trip +
A5
Close Coil -
A6
MPSC-2000 VIM
A7
Charge Motor -
A8
Local Elec. Close +
A9
Local Elec. Trip +
A10
Alarm Switch
A11
Alarm Switch
A12
Alarm Switch
A13
Alarm Switch
A14
Aux. Sw. "a" +
A15
Aux. Sw. "a" -
A16
Aux. Sw. "a" +
A17
Aux. Sw. "a" -
A18
Aux. Sw. "b" +
A19
Aux. Sw. "b" -
A20
Aux. Sw. "a" +
A21
Aux. Sw. "a" -
A22
Aux. Sw. "b" +
A23
Aux. Sw. "b" -
5
A24
(Spare)
A25
(Not Used)
pin-out assignments.
(6) The assignments for pins B3 - B6 will differ depending on whether the DESP option has been supplied. See
the MPSC-2000 schematic supplied with the breaker.
Pin
Description
B1
Undervoltage Trip Device +
B2
Undervoltage Trip Device -
B3
(MPSC-2000 4WG or DESP)
B4
(MPSC-2000 4WG or DESP)
B5
(MPSC-2000 4WG or DESP)
B6
(MPSC-2000 4WG or DESP)
B7
Aux. Sw. "a" +
B8
Aux. Sw. "a" -
B9
Aux. Sw. "b" +
4
B10
Aux. Sw. "b" -
4
B11
Aux. Sw. "a" +
4
B12
Aux. Sw. "a" -
4
B13
Aux. Sw. "b" +
B14
Aux. Sw. "b" -
B15
Aux. Sw. "a" +
B16
Aux. Sw. "a" -
B17
Aux. Sw. "b" +
B18
Aux. Sw. "b" -
B19
Aux. Sw. "a" +
B20
Aux. Sw. "a" -
B21
Aux. Sw. "b" +
B22
Aux. Sw. "b" -
B23
(Spare)
B24
(Spare)
B25
(Not Used)
5
5
IB 6.2.11.1-1C
Notes:
(1) These
assignments
provided for reference only,
and may be changed due to
6
special requirements. Some
pins or plugs may not be
6
present
on
6
configurations.
breaker
schematic
6
diagram(s) for details.
(2) Note the polarity of control
devices: "+" is the send and
"-" is the return.
(3) The two terminals of each
Auxiliary Switch contact are
connected
Secondary Disconnect pins.
For example, pins A14 and
A15 are connected to a
single "a" contact. Also, the
polarity signs are provided
on these pins for consistency
only;
the Auxiliary Switch
contacts
are
sensitive.
(4) The Alarm Switches can be
wired in two different ways.
See the schematic supplied
with the breaker for details
on the pin-outs.
(5) The pins marked "(Spare)"
may
be
used
b r e a k e r s
f o r
c u s t o m e r
requirements.
schematic
wiring
supplied with the breaker for
Page 12