E: 72. Compressor Thermistor Error (Outdoor Unit) - Fujitsu AUXG36KRLB Service Manual

Cassette type
Hide thumbs Also See for AUXG36KRLB:
Table of Contents

Advertisement

2-22. E: 72. Compressor thermistor error (Outdoor unit)

Wired remote
Indicator
controller
Outdoor unit main PCB
Detective actuator
Compressor temperature thermistor
Forecast of cause
Check point 1. Check connection of connector
Check if connector is loose or removed.
Check erroneous connection.
Check if thermistor cable is open
→ Reset power when reinstalling due to removed connector or incorrect wiring.
Check point 2. Remove connector and check thermistor resistance value
For the compressor thermistor resistance value, refer to
values"
on page 03-61.
If thermistor is either open or shorted, replace it and reset the power.
Check point 3. Check voltage of main PCB
Make sure circuit diagram of outdoor unit and check terminal voltage at thermistor
(DC 5.0 V).
NOTE: For details of thermistor connector, refer to "Wiring diagrams" in Chapter 2.
TECHNICAL DATA AND PARTS LIST.
If the voltage does not appear, replace main PCB.
2-22. E: 72. Compressor thermistor error (Outdoor unit)
Error code
When compressor temperature thermistor open or short
circuit is detected at power on or while running the
compressor
End
- (03-27) -
E: 72
Connector failure
Thermistor failure
Main PCB failure
"Thermistor resistance
2. Troubleshooting with error code