3-4. No cooling/No heating

Forecast of cause
Check point 1. Check Indoor unit
Does Indoor unit fan run in the HIGH mode?
Is air filter dirty?
Is heat exchanger clogged?
Check if energy save function is operated.
Check point 2. Check outdoor unit operation
Check if outdoor unit is operating.
Check any objects that obstruct the air flow route.
Check if heat exchanger is clogged.
Is the valve open?
Check point 3. Check site condition
Is capacity of Indoor unit fitted to the room size?
Any windows open or direct sunlight?
Check point 4. Check Indoor/ Outdoor installation condition
Check connection pipe (specified pipe length and pipe diameter?)
Check any loose or removed communication line.
→ If there is an abnormal condition, correct it by referring to the installation manual or the "DESIGN
& TECHNICAL MANUAL".
Check point 5. Check Refrigeration cycle
Check if strainer is clogged (Refer to the figure below).
Measure gas pressure, and if there is a leakage, correct it.
Check the electronic expansion valve.
Refer to outdoor unit Electronic Expansion Valve (EEV) in
formation"
on page 03-52.
Check compressor.
Refer to compressor in
Refer to inverter compressor in
NOTE: When recharging the refrigerant, make sure to perform vacuuming,
and recharge the specified amount.
3-4. No cooling/No heating
"Service parts information"
"Service parts information"
End
- (03-48) -
Indoor unit error
Outdoor unit error
Effect by surrounding environment
Connection pipe/Connection wire failure
Refrigeration cycle failure
"Service parts in-
on page 03-52.
on page 03-52.
MPa MPa
3. Troubleshooting without error code

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Auxg45krlbAuxg54krlbAoyg36krtaAoyg45krtaAoyg54krta

Table of Contents