E: 84. Current Sensor Error (Outdoor Unit) - Fujitsu AUXG36KRLB Service Manual

Cassette type
Hide thumbs Also See for AUXG36KRLB:
Table of Contents

Advertisement

2-26. E: 84. Current sensor error (Outdoor unit)

Wired remote
Indicator
controller
Detective actuator
Outdoor unit
Forecast of cause
Check point 1. Reset power supply and operate
Does error indication show again?
Check point 2. Check connections of outdoor
unit electrical components
Check if the terminal connection is loose.
Check if connector is removed.
Check erroneous connection.
Check if cable is open.
Check point 3. Replace main PCB
If Check point 1, 2 do not improve the symptom,
change main PCB.
Check point 1-2. Check external cause at Indoor and Outdoor (Voltage drop or Noise)
Instant drop: Check if there is a large load electric apparatus in the same circuit.
Momentary power failure: Check if there is a defective contact or leak current in the power sup-
ply circuit.
Noise: Check if there is any equipment causing harmonic wave near electric line. (Neon bulb or
electric equipment that may cause harmonic wave)
Check the complete insulation of grounding.
2-26. E: 84. Current sensor error (Outdoor unit)
Error code
main PCB
End
End
When input current sensor has detected 0 A, while
inverter compressor is operating at higher than 56 rps,
after 1 minute upon starting the compressor. (Except
during the defrost operation)
Defective connection of electric components
External cause
Main PCB failure
If no, go to
"Check point
Upon correcting the removed connector or mis-
wiring, reset the power.
- (03-31) -
E: 84
1-2".
2. Troubleshooting with error code

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Auxg45krlbAuxg54krlbAoyg36krtaAoyg45krtaAoyg54krta

Table of Contents