Initial operation

6.1.2 Tolerance of power operated shutdown

In some cases the drive will not shut down correctly during or after initial operation.
Or the drive stops, before it has reached the end position. This particularly happens,
when a very heavy or a very lightweight wing is used.
Motor overload
Damage of components by motor overload.
 Check after any change of configuration, if the control
device shuts down correctly.
 Do not set tolerance too high.
When the drive stops early
 Turn potentiometer 2 (P2) clockwise
 Drive switches off later
When the drive does not stop
 Turn potentiometer 2 (P2) counterclockwise
 Drive switches off sooner
Hint
After a maximum operating time of 5 minutes, the drive switches off in
any case.
24V 50VA Motor control box -
Version 1.0
w w w . b a i e r - g m b h . d e
N O T I C E
6
Increase tolerance
Decrease tolerance
Instruction Manual
15/20