1
1-3. Refrigerant Flow Diagram
Outdoor Units: U-100PE1E5A
U-100PE1E8A
High pressure
switch
Discharge Temp
Thermistor
Compressor
1
1-4. Operationg Range
Type PE1
Cooling
Heating
4-way
valve
Muffler
Muffler
Suction Temp
Thermistor
Accumulator
Cooling cycle
Heating cycle
Temperature
Indoor air intake temp.
Maximum
32°C DB / 25°C WB
Minimum
18°C DB / 14°C WB
Maximum
30°C DB / − WB
Minimum
16°C DB / − WB
Outdoor-air
Temp Thermistor
Heat exchanger
Temp Thermistor
EC
Heat
exchanger
P
Defrost Temp
Thermistor
Distributor
Strainer
Strainer
Expantion
valve
1-220
Indoor Unit
ø15.88
Heat
exchanger
Distributor
Strainer
ø9.52
Outdoor air intake temp.
46°C DB
-15°C DB
24°C DB/18°C WB
-20°C DB / -20°C WB