Installation Procedure For Venting System Through Walls - Watts Aerco Modulex EXT Series Technical Application Manual

Venting & combustion air guide
Hide thumbs Also See for Aerco Modulex EXT Series:
Table of Contents

Advertisement

Modulex EXT Vent and Combustion Air Application Guide
NOTE:
Specific installation regulations for side-wall and vertical terminations, respectively, are described in the
following two sections (Sections 3.2 and 3.3).
3.2. INSTALLATION PROCEDURE FOR VENTING SYSTEM THROUGH
WALLS
The minimum distances from adjacent public walkways, adjacent buildings, operable windows and
building openings shall not be less that those values specified in the National Fuel Gas Code, ANSI
Z223.1 and/or CAN/CGA B149, Installation Codes.
Minimum clearance of 4 feet (1.22 m) horizontally from, and in no case above or below, unless a 4-
foot (1.22 m) horizontal distances is maintained, from electric meters, gas meters, regulators and
relief equipment.
Refer to the notes below and Figure 19, when determining the location of the vent outlet.
a) At least 12 inches (31 cm) above finished grade, or at least 12 inches (31 cm) above the
normally expected snow accumulation level in geographical areas where snow accumulates.
With a vent termination clearance of at least 4 feet (122 cm) from any air openings into a
building.
b) In Massachusetts, when side-wall venting is used, the vent termination must be located a
minimum of 4 feet above grade. For detailed information pertaining to side-wall venting within
the Commonwealth of Massachusetts, refer to pages 8 and 9 in the MLX EXT manual, GF-
136.
c) At least 3 feet (92 cm) above any forced air inlet located within 10 feet (305 cm).
d) At least 4 feet (122 cm) horizontally from electric meters, gas meters, regulators and relief
equipment.
e) For horizontal runs, keep vent pipes away from any combustible material, electric wires, and
building insulation.
f) Do not terminate vent over public walkways or over an area where condensate or vapor could
create a nuisance or hazard or could be detrimental to the operation of regulators, relief
valves, or other equipment.
g) Do not locate the vent termination too close to shrubbery as flue products may stunt growth or
kill them.
h) Some building materials may be affected by flue products expelled near unprotected surfaces.
Sealing or shielding of exposed surfaces with a corrosion resistant material (such as aluminum
sheet) may be required to prevent staining or deterioration.
See the National or Canadian Codes listed at the beginning of these instructions for additional
information on termination location.
Page 22 of 28
09/25/2017
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913
Phone: 800-526-0288
TAG-0054-0F
GF-136-V

Advertisement

Table of Contents
loading

Table of Contents