Installing and Connecting the Assembly Pipe of the Indoor Unit

A
C
10
E-
Connect indoor and outdoor units with field-supplied copper pipes by means
of flare connections. Use insulated seamless refrigeration grade pipe only, (Cu
DHP type according to ISO1337), degreased and deoxidized, suitable for op-
erating pressures of at least 4200 kPa and for burst pressure of at least 20700
kPa. Under no circumstances must sanitary type copper pipe be used.
There are 2 refrigerant pipes of different diameters:
The smaller one is for the liquid refrigerant
The larger one is for the gas refrigerant
A short pipe is already fitted to the air conditioner. You may need to extend the
pipe using the assembly pipe (optional).
B
The connection procedure for the refrigerant pipe varies according to the exit
position of the pipe when facing the wall:
Right(A)
Left(B)
Underside(C)
Rear
1
Cut out the appropriate knock-out piece (A, B, C) on the rear of the indoor unit
unless you connect the pipe directly from the rear.
2
Smooth the cut edges.
3
Remove the protection caps of the pipes and connect the assembly pipe
to each pipe. Tighten the nuts first with your hands, and then with a torque
wrench, applying the following torque:
Outer Diameter
ø6.35 mm
ø9.52 mm
ø12.70 mm
ø15.88 mm
ø19.05 mm
ø22.23 mm
Note
If you want to shorten or extend the pipes, refer to page 12.
4
Cut off the remaining foam insulation.
5
If necessary, bend the pipe to fit along the bottom of the indoor unit.
Then pull it out through the appropriate hole.
 The pipe should not project from the rear of the indoor unit.
 The bending radius should be 100 mm or more.
6
Pass the pipe through the hole in the wall.
7
For further details on how to connect to the outdoor unit and purge the air,
refer to page 11.
CAUTION
Tighten the flare nut with torque wrench according to specified method.
If the flare nut is over-tightened, the flare may break and cause
refrigerant gas leakage.
DO NOT WALL UP THE PIPE CONNECTION !
All refrigerant pipe connection must be easy accessible and serviceable.
Thickness
Torque (kgf•cm)
0.8mm
140~170
0.8mm
250~280
0.8mm
380~420
1.0mm
440~480
1.0mm
990~1210
1.0mm
990~1210