Calibration (Cont'd)
8.
8.2.3. Air-gap adjustment
Air-gap between the proximity switch and the arm is
factory adjusted. If new adjustment is required
proceed as follows:
• Loosen the proximity sensor nut (37A), located on
the front of the bracket (36).
• Unscrew a few turns the locknut (37B) located on
the back of the bracket.
Parts List
Rep.
Designation
3
Screw
6
Housing
7 (1) O-ring
8
Snap ring
9
Safety screw
10 (1) O-ring
11
Axis
(1) Recommended spare parts
18
|
Baker Hughes
8
3
7
25
Rep.
Designation
12
Cover
14
Serial plate
19
Spacer
24
Terminal block
25
Terminal block
30
Spacer
(2) Only for 496-4 model
• Position the arm above the proximity sensor
and push the shaft end (11) towards the
outside of the housing so as to eliminate the
longitudinal play.
• Hold in position the proximity sensor and screw the
nut (37A). Adjust air gap to 0,3 mm using a shim
• Tighten the lock nut (37B).
6
9
10
11
34
37B
Rep.
31
Snap ring
32
Washer
33
Arm
34
Proximity sensor
35 (2) Spacer (Not shown)
36
Sensor bracket
37
Nut
© 2020 Baker Hughes Company. All rights reserved.
12
8
30
37A
31
32
33
36
15
14
3
24
19
Designation

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Masoneilan 496-857Masoneilan 496-858

Table of Contents