5. ATEX Flameproof Marking and Electrical Safety
Parameters
5.1 Marking
The marking is on the serial plate stamped on the
496 cover (rep 14).
•
Name and address of the manufacturer
Dresser Produits Industriels S.A.S.
14110 CONDE SUR NOIREAU – FRANCE
•
Type designation:
– 496-857 for position transmitter
– 496-857/• for position transmitter with
additional function(s)
The • can be replaced by 1, 2, 4, 5, 6, 7
– 496-•57 for position switches
The • can be replaced by 1, 2, 4, 5, 6, 7
– 496-157/• and 496-257/• for position switches
with additional function(s)
The • can be replaced by 1, 2
•
the specific marking:
•
the complementary marking:
For position switch(es) 496-•57 and 496-•57/•
and position transmitter with or without additional
function(s) 496-857 and 496-857/•
– Ex db IIC T6 Gb Ta –55°C, +75°C (*)
Ex tb IIIC T85°C Db IP66/IP67
– Ex d IIC T5 Gb Ta –55°C, +85°C (*)
Ex tb IIIC T100°C Db IP66/IP67
(*) Ambient temperatures ranges and surface
temperatures for the temperature classifications T6, T5
and T4 are given in Annex II with the different possible
combinations allowed.
•
Serial number
•
Year of manufacturing
•
Number of notified body
•
EC-Type examination certificate number
AVERTISSEMENT : NE PAS OUVRIR SOUS TENSION
WARNING : DO NOT OPEN WHEN ENERGIZED
Warning
AVERTISSEMENT : DANGER POTENTIEL DE
CHARGES ELECTROSTATIQUES – VOIR
INSTRUCTIONS
WARNING: POTENTIAL DANGER OF ELECTROSTATIC
CHARGES. SEE INSTRUCTIONS
10
|
Baker Hughes
II 2 GD
••••
Warning
WARNING
AVERTISSEMENT : NE PAS OUVRIR SI UNE ATMOSPHERE
EXPLOSIVE GAZEUSE EST PRESENTE
WARNING: DO NOT OPEN WHEN AN EXPLOSIVE GAS
ATMOSPHERE IS PRESENT
•
T cable:
Mandatory mention when the ambient temperature is
higher than 70°C.
T ambient
70°C
75°C
80°C
85°C
5.2 Electrical safety parameter
•
Maximum dispersed power = 5W
•
Voltage supply allowable:
Min Voltage
Type
496-157 or
496-257 or
496-657 or
496-757
496-457 or
496-557
Pepperl &
Fuchs
496-457 or
496-557
Télémécanique
496-857/•
(direct current)
© 2020 Baker Hughes Company. All rights reserved.
T cable
75°C
80°C
85°C
90°C
Max Voltage
220V
(direct current) or
-
250V
(alternative current)
16V
-
(direct current)
58V
-
(direct current)
9.0V
36V
(direct current)