Table 2.13-1 Standard Timings; Table 2.13-2 49 Results; Table 2.13-3 Capacity Alarm; Table 2.13-4 Element Blocking - Siemens 7PG2113 Technical Manual

Feeder protection
Hide thumbs Also See for 7PG2113:
Table of Contents

Advertisement

Time Constant (mins)
1
2
3
4
5
10
15
20
25
30
50
100
The Thermal State must be in the fully reset condition in order to measure the operate time correctly. This can be
achieved by setting change in the Thermal protection settings menu or by pressing the Test/Reset button when
the Thermal Meter is shown in the Instruments Mode.
Reset the thermal State then apply 2x the Overload Setting current.
Calculated Operate Time (s)
If the Thermal Overload Capacity Alarm is used, this can be tested by monitoring the Thermal Capacity in the
instruments menu. If the Thermal time constant is longer than a few minutes, this can be assessed during the
timing test above. If the Time Constant is less than a few minutes, a lower multiple of current will be required such
that the rate of capacity increase is slowed to allow monitoring of the instrument to be accurate.
Capacity Alarm Setting
2.13.1.1
Element Blocking
The Thermal element can be blocked by Binary Input Inhibit. This functionality should be checked.
Element
49
©2010 Siemens Protection Devices Limited
7PG2113/4/5/6 Commissioning & Maintenance
Table 2.13-1
Standard Timings
Table 2.13-2
49 Results
Table 2.13-3
Capacity Alarm
Table 2.13-4
Element Blocking
Operate Time (sec)
17.3
34.5
51.8
69
86.3
173
259
345
432
51.8
863
1726
Measured Operate Time (s)
Measured
BI Inhibits
Chapter 6 Page 53 of 77

Advertisement

Table of Contents
loading

This manual is also suitable for:

7pg21147pg21157pg2116

Table of Contents