Technical Data - D+H DXD 300-BSY+ Original Instructions Manual

Table of Contents

Advertisement

Available languages

Available languages

Technical data

Type
Power supply
Nominal current
Nominal force
Nominal locking force
Lifetime
Duty cycle
Housing
Ingress protection
Temperature range
Fire stability
Emission sound pressure
level
Nominal stroke length*
Additional functions *
* programmable with software SCS
Normal operation =
SHEV- fast running =
Forces
DXD 150-BSY+ (-HS) DXD 300-BSY+ (-HS)
OPEN
1500 N
CR III
1000 N
CR II
1000 N
CR I
800 N
Closing edge protection
In "CLOSE" direction the drive has an active
protection for the main closing edge. With an
overload in the closing range 3 and 2 the drive runs
"OPEN" for 10 seconds, then drive "CLOSE" again. If
after three attempts a closing is not possible, the
drive remains in this position.
In addition, the drive has a passive clamping
protection. The closing speed in closure Range 2
and 1 is reduced to 5 mm/s.
Higher forces can occur on besides
closing edges. Danger of violent
pressure in handaccessible area.
99.824.27 1.4/05/18
DXD 150-BSY+
DXD 150-BSY+ HS
24 V DC, ±15 %
24 V DC, ±15 %
1,4 A
2,5 A
1500 N
1500 N
1100 N
>20 000 double strokes
30 % (with cycle time 10 minutes)
aluminium powder-coated / polycarbonate
IP 64 ("-W" = IP 54)
-5 ... +75 °C
30 min / 300 °C
LpA ≤ 70 dB(A)
see type plate
closing edge protection activated (3 stroke repeatings)
3000 N
2000 N
All forces
1600 N
+ app. 20 %
800 N
switch-off reserve (temporary)
English
DXD 300-BSY+
24 V DC, ±15 %
2,5 A
3000 N
2200 N
Running speed and forces
depending on magnet position
main closing edge
DXD 300-BSY+ HS
24 V DC, ±15 %
5,0 A
3000 N
7/16
DXD-BSY+ (-HS)

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Dxd 150-bsy+Dxd 150-bsy+ hsDxd 300-bsy+ hs

Table of Contents