TABLE 4
Interval
Item to be
inspected
1 Insulating parts.
1 year or
50,000 operations.
1 year or
2 Structure.
50,000 operations.
3 Interrupter.
1 year or
50,000 operations.
In case of accidental
impacts.
4 Interrupter contacts.
1 year or
50,000 interruptions
at the rated current.
1 year or
5 Auxiliary contacts.
50,000 operations.
6 Auxiliary circuit conduc-
1 year or
50,000 operations.
tors.
7 Visual inspection of the iso-
5 years or
lating contacts (withdrawa-
5.000 operations.
ble contactors)
7.3. Servicing
Carry out the checks described below.
Item to be
Interval
serviced
1 Contactor.
2 years or
100,000 operations.
2 Contactor springs.
2 years or
100,000 operations.
3 Power connections.
2 years or
100,000 operations.
4 Earthing contact
2 years or
(fixed contactors).
100,000 operations.
5 Insulation resistance.
2 years or
100,000 operations.
6 Racked-in/isolated aux-
2 years or
iliary contacts in the
100,000 operations.
truck.
Operation to be carried out
Visual inspection of the insulating parts. The insulating parts must
be free of any accumulation of dust, humidity, dirt (clean), cracks,
traces of surface discharges or damage.
Visual inspection of the structure and mechanisms. The components
must be free of any deformation, accumulation of dust, dirt or dam-
age. The screws, nuts and bolts must be correctly tightened. Avoid
touching the ceramic surface.
Check that the interrupter is free of accumulation of dust, dirt (clean),
cracks (replace), traces of surface discharges or damage.
Carry out a voltage test with the contacts open at 15 kV - 50 Hz for
one minute. If there is a discharge during the test, the interrupter
must be replaced because this type of phenomenon corresponds to
deterioration in the degree of vacuum. In case of need, contact ABB
Service.
Refer to fig. 16. The contact material vaporises from the surfaces
during each interruption and condenses elsewhere inside the vacuum
interrupter. This is a normal process, and is foreseen by the overrun,
or by the wear tolerance.
As the contacts wear, the overrun distance "M" decreases. When
distance "M", of any pole, goes below 0.5 mm with the contactor in
the closed position, all the sub-assemblies must be replaced.
Use a fork-shaped gauge 0.5 mm thick to carry out this measure-
ment.
Caution! Never attempt to adjust the nuts of the vacuum inter-
rupters for any reason whatsoever.
The overrun distance must be checked, but not adjusted.
Check correct operation and the signals.Check that there are no burnt
or worn contacts (replace).
Check whether any cabling straps are loose or broken and check
connection tightness.Examine all the wire or cable connections to
make sure that none of them are loose and that there is no over-
heating.
The isolating contacts must be free of any deformation or erosion.
Lubricate the contact elements with 5RX Moly type grease.
Operation to be carried out
Carry out five mechanical closing and opening operations. The con-
tactor must operate regularly without stopping in intermediate posi-
tions.
Check integrity of the springs.
Check tightness: M8 bolt = 19 Nm; M10 bolt = 33 Nm.
Check there are no traces of overheating or oxidation.
Check tightness of the connections.
See par. 6.1.
Check that the signals are correct.
Furthermore the following is
recommended:
– replacement of the inter-
rupters after 250,000 op-
erations;
– replacement of the auxil-
iary contacts after 300,000
operations.
29