Binary input wave

Advertisement

Binary Input wave AP 261
First the radio
controlled sensor (D1), as shown in Diagram
-
D, must be placed onto the mounting plate (D2). You
should then slide it in the direction of the arrow until the
clamps (D3) click into place.
1.
D3
Diagram D
Dimension Diagram
Dimensions in mm
36
32
87 72
Connection of an External Contact
An external contact can be connected to the binary input
wave via plug-in terminals (C3) on the rear of the radio-
controlled sensor. The external contact can be con-
nected electrically in series with the reed contact in the
radio-controlled sensor or can be used on its own.
Note: Due to the low voltage and low current levels that
are used for the contact surveillance (to ensure a long
battery life time), only encapsulated contacts as those of
reed relays or measuring relays should be used.
Use internal contact only
Diagram E1 indicates the plug-in terminals of the binary
input in the supplied state. It has been set via the wire
jumper between terminals 3 and 4 that only the internal
contact is used.
Siemens AG
Automation and Drives Group
Electrical Installation Technology
P.O. Box 10 09 53, D-93009 Regensburg
Use external contact only
Diagram E2 indicates the terminal assignment when only
an external contact should be used. The internal contact
has been deactivated via the wire jumper between ter-
minals 1 and 2.
D1
Use internal and external contact
Diagram E3 indicates the terminal assignment if the in-
ternal and an external contact should be used together.
2.
The wire jumper is omitted in this case.
1 2 3 4
D2
Diagram E1
Strain relief
The cable can be fixed to the external contact via the
supplied clamping plate (C5). The maximum permitted
diameter of the connecting cable is 5 mm.
Note: The binary input sends a switching command OFF
27
when the internal contact or an external contact is closed
and an ON switching command when they are opened.
Location and Function of the Display and
Operating Elements
Diagram A
A1
A2
Diagram C
C1
C2
C3
Commissioning
Note
When commissioning a binary input wave, it must be
linked via "learning telegrams" to the KNX radio-
controlled devices which should process its radio tele-
grams. Only those radio-controlled devices which are
able to process a switching command (ON/OFF) can be
connected to a binary input. These devices are e.g. a
universal dimmer insert sys or a switch insert sys in con-
wave AP 261, 4 pages
 Siemens AG 2005
Subject to change without prior notice
Technical Product Information
1 2 3 4
Diagram E2
LED for displaying the sending of a radio tele-
gram, the link with other radio-controlled compo-
nents and a low battery
Push button for linking the binary input with other
radio-controlled components
Battery compartment
Battery
Plug-in terminals for setting whether an external
contact should be used as well as for the connec-
tion of an external contact
Update: http://www.siemens.de/gamma
instabus rf
January 2005
5WG3 261-3AB11
1 2 3 4
Diagram E3
Technical Manual
2.20.3.2/3