Attention: Accidentally connecting any of the 24 VDC wires to the RS-485 wiring
Table 2 Maximum Wiring Run to Last Annunciator
Max for all
Annunciators
Amperes
0.12
1180
0.30
470
0.60
235
0.90
156
1.20
118
1.50
1.70
4.0
DIP Switch Settings
Each RAX-LCD Shared Display Annunciator needs to be assigned a unique address via the
switch SW1. The RAX-LCD DIP switches are set as:
SW1-1
SW1-2
SW1-3
SW1-4
SW1-5
SW1-6
SW1-7
SW1-8
The OFF setting is active. The addresses available for the RAX-LCD are 33 to 63. Set the
address as follows in the table below:
4
All circuits are power limited and must use type FPL, FPLR, or FPLP power
limited cable.
will result in damage to the annunciator and/or to the fire alarm control
panel to which it is connected.
18AWG
16AWG
ft
m
ft
360
1850
567
143
750
229
71
375
114
47
250
36
185
94
29
150
78
24
125
=
Address A0
=
Address A1
=
Address A2
=
Address A3
=
Address A4
=
Address A5(OFF)
=
not used
Put in "OFF" position
for firmware restore
=
during power up. At
all other times put in
"ON" state.
14AWG
m
ft
m
3000
915
4250
1200
366
1900
600
183
850
76
400
122
570
56
300
91
425
46
240
73
343
38
200
61
285
DIP SWITCH SETTINGS
1
DIP switches are for assigning an address to the RAX-LCD.
Binary addresses 33 to 63 are available with the least
significant bit being switch SW-1 and the most significant bit
being SW-6. The OFF setting is active binary. DIP switches
SW1-7 and SW1-8 are not used. For example, address 33 is
set by setting SW1-6 and SW1-1 OFF and all the other DIP
switches are ON.
Max Loop
Resistance
12AWG
ft
m
Ohms
1296
15
579
6
259
3
174
2
129
1.5
105
1.2
87
1.0
ON
OFF
8
SW1
Need help?