ABB ACS880-307LC Hardware Manual page 43

Diode supply units
Table of Contents

Advertisement

3. Strip off the cable plastic sheath above the entry plate just enough to ensure proper
connection of the bare shield and the EMI conductive cushions.
4. Tighten the two tightening screws so that the EMI conductive cushions press tightly
round the bare shield.
1
Note 1: Keep the shields continuous as close to the connection terminals as possible.
Secure the cables mechanically at the entry strain relief.
Note 2: If the outer surface of the shield is non-conductive:
Cut the shield at the midpoint of the bare part. Be careful not to cut the conductors or
the grounding wire (if present).
Turn the shield inside out to expose its conductive surface.
Cover the turned shield and the stripped cable with copper foil to keep the shielding
continuous.
A
2
1
5
Note for top entry of cables: When each cable has its own rubber grommet, sufficient IP
and EMC protection can be achieved. However, if there is more than one cable per grommet,
plan the installation beforehand as follows:
1. Make a list of the cables coming to the cabinet.
2. Sort the cables going to the left into one group and the cables going to the right into
another group to avoid unnecessary crossing of cables inside the cabinet.
3. Sort the cables in each group according to size.
4
B
C
A
B
C
1
2
3
2
4
3
4
Electrical installation 43
3
2
Stripped cable
Conductive surface of the shield exposed
Stripped part covered with copper foil
Cable shield
Copper foil
Shielded twisted pair
Grounding wire
11