HR1S-ATE Operation Chart
Power ON
Start
With Start Switch
Emergency Stop Switch (NC1)
Transistor Output Y89 (S12)
Emergency Stop Switch (NC2)
Transistor Output Y90 (S22)
Start Switch
Start Switch
Without Start Switch
Emergency Stop Switch
(NC2 or NC1)
Transistor Output Y89 (S12)
Emergency Stop Switch
(NC1 or NC2)
Transistor Output Y90 (S22)
Start Switch
Output
External Start Conditions
Output 13-14 (NO)
Output 23-24
NO
(
)
Output 57-58 (NO
)
Output 67-68 (NO
)
Output 77-78 (NO
)
Transistor Output Y88 (A1/A2
)
Transistor Output Y91 (Stop1)
Residual Risk
(EN ISO/ISO12100-1)
The wiring diagrams on previous page have been tested under actual oper-
ating conditions. The HR1S-ATE safety relay module can be used in a safety
circuit by connecting to safety equipment compliant to applicable standards.
Consider residual risk in the following circumstances:
a) When it is necessary to modify the recommended circuit and if added/
modified components are not properly integrated into the control circuit.
b) When applicable standards of machine operation are not observed, or
Instructions
Only persons with technical expertise may install, startup, modify, or
retrofit the HR1S-ATE safety relay module.
Turn the power off before installation, removal, wiring, maintenance, or
inspection of the safety relay module. If an error occurs, line voltage may
be present at the control circuit in devices without DC isolation.
Observe all electrical safety regulations issued by appropriate technical
authorities or trade association. The safety function can be lost if the
device is not used for its intended purpose.
Do not open the housing or perform invalid operation, otherwise the war-
ranty will become voided.
Negligence to observe the following instructions may cause accidents
that may result in death or serious injuries.
Connect the wires according to the wiring diagrams shown on previous
page.
Connect the wires according to applicable standards.
The contacts of relays and contactors to connected with safety outputs
must be forced guided (compliant with EN 50205).
For external fusing, use an appropriate fuse size and connect according
to the wiring diagram on previous page.
When maintaining or adjusting machines, observe the maintenance
schedule.
If the recommended circuit is modified or if components are added/modi-
fied, make sure that they are properly integrated into the control circuit.
Relays must have mechanically-linked contacts.
Follow required standards applicable to the operation of the machine.
When maintaining or adjusting machines, observe a proper maintenance
schedule.
IDEC Corporation
Emergency Stop
Emergency Stop
Not Operated
Operated
When monitoring the start switch,
with Y3-Y5 jumpered
(default setting/recommended)
When monitoring the start switch,
with Y3-Y4 jumpered
tmax.= 75ms∗
∗When using without start switch,
the input synchronization time
should be 75 ms max.
Without start switch,
with Y3-Y4 and S33-Y1 jumpered
Operation
ON
Tv = 0 to 30 seconds
adjustable
1175 Elko Drive
Sunnyvale, CA 94089
©2011 IDEC Corporation. All Rights Reserved. 06/11 PDF only.
Output Contact Electrical Life
(Safety Circuit, Time-delay Circuit, Auxiliary Circuit)
DC13: 24V
(<0,1Hz)
AC15:
230V
OFF
when the machine is not adjusted or maintained properly (adhere to a
strict maintenance schedule).
c) When the contacts of relays and contactors for connected with safety
outputs are not forced guided (compliant with EN 50205).
Do not use the module if it has been subjected to improper or incorrect
use. In this case, the warranty will be voided.
Do not use the HR1S-ATE in conditions where irregular voltage, current,
temperature, or humidity could occur.
Before starting up your equipment for the first time, be sure to check all
safety functions according to regulations and observe the specified test
cycles for safety equipment.
Perform the following precautionary steps prior to installation, assembly,
or disassembly of the system.
1. Disconnect the supply voltage to the equipment / system prior to
starting work.
2. To prevent accidental activation of the module or system, perform
lock-out or tag-out.
3. Make sure that no voltage is applied.
4. Ground N (–) as shown in the wiring diagram on previous page.
5. Use guards or barriers to protect against components operating
adjacent to the safety relay module.
6. The devices must be installed in a cabinet with a protection class of
at least IP54.
Contact Protection
Type of protection according to EN/IEC 60529
Housing / Teminals: IP40 / IP20
Finger-safe protection according to EN 50274
Connect external fuse according to the wiring diagram on page 3.
Specifications and other descriptions in this document are subject to change without notice.
800-262-IDEC (4332)
Fax: 408-745-5258
DC1: 24V
AC1:
230V
Operations