3 2 | Bosch Climate 5000 Series Ductless Air Conditioner / Heat Pump Multi Zone Outdoor Units
Number of Presses
Display
22
Indoor unit A room temperature (T
23
Indoor unit B room temperature (T
24
Indoor unit C room temperature (T
25
Indoor unit D room temperature (T
26
Indoor unit E room temperature (T
27
Indoor unit A evaporator temperature (T
28
Indoor unit B evaporator temperature (T
29
Indoor unit C evaporator temperature (T
30
Indoor unit D evaporator temperature (T
31
Indoor unit E evaporator temperature (T
32
Condenser pipe temperature (T3)
33
Outdoor ambient temperature (T4)
34
Compressor discharge temperature (TP)
35
AD value of current
36
AD value of voltage
37
EXV open angle for A indoor unit
38
EXV open angle for B indoor unit
39
EXV open angle for C indoor unit
40
EXV open angle for D indoor unit
41
EXV open angle for E indoor unit
42
Frequency limit symbol
43
Average value of T2
44
Outdoor unit fan motor state
45
The last error or protection code
46
F indoor unit capacity
47
F indoor unit capacity demand code
48
F indoor unit evaporator outlet temperature (T
49
F indoor unit room temperature (T
50
F indoor unit evaporator temperature (T
51
EXV open angle for F indoor unit
Table 18
Data subject to change
A)
1
B)
1
C)
1
D)
1
E)
1
A)
2
B)
2
C)
2
D)
2
E)
2
If the temperature is higher than 99 °C, the display will show a decimal point. For
If the value is higher than 99, the digital display will show a decimal point.
Bit7
Bit6
Bit5
Bit4
Bit3
Bit2
Bit1
Bit0
(Sum T2 value of all indoor units)/(number of indoor units with good connection)
Off: 0, High speed: 1, Med speed: 2, Low speed: 3, Breeze: 4, Super breeze: 5
F)
2B
F)
1
F)
2
Remark
If the temperature is lower than 0 °C, the digital display shows "0."
If the temperature is higher than 50 °C, the digital display shows "50."
If the indoor unit is not connected, the digital display shows: "
If the temperature is lower than -9 °C, the digital display shows "-9."
If the temperature is higher than 70 °C, the digital display shows "70."
If the indoor unit is not connected, the digital display shows: "
The display value is between 30–129 °C.
If the temperature is lower than 30 °C, the digital display shows "30."
example, if the digital display shows "0.5",
the compressor discharge temperature is 105 °C.
The display value is a hex number. For example, the digital
display tube shows "Cd", it means AD value is 205.
The display value is a hex number. For example, the digital
display tube shows "Cd", it means AD value is 205.
Actual data/4.
For example, if the digital display shows "2.0",
the EXV open angle is 120×4=480 pulse.
Frequency limit caused by IGBT radiator
Frequency limit caused by PFC
Frequency limit caused by T4.
Frequency limit caused by T2.
Frequency limit caused by T3.
Frequency limit caused by T5.
Frequency limit caused by current
Frequency limit caused by voltage
00 means no malfunction and protection
08.2020 | Bosch Thermotechnology Corp.
Service Manual
"
"
The display value is a
hexidecimal number. For
example, the digital display
show 2A, then Bit5=1,
Bit3=1, and Bit1=1. This
means that
a frequency limit may be
caused by T4, T3, or the
current.