General Instructions
Read these instructions carefully before
installation and use. Keep this manual for
future reference.
The product may only be used as set out in
the assembly and operating instructions. The
guarantee is only valid if the product is used
in the manner intended and in accordance
with the instructions.
Application
PAEC3200C-NA is a compact air curtain with
a recommended installation height of up to
3.2 metres/10.5 feet. The air curtain has
an integrated control system and can be
remotely controlled.
The air curtain is available without heat,
with electrical heating and with water heating.
Protection class for units with electrical
heating: IP20.
Protection class for units without heating and
units with water heating: IP21.
Operation
Air is drawn in at the top of the unit and
blown out downwards so that it shields the
door opening and minimizes heat loss. To
achieve the optimum curtain effect the
unit must extend the full width of the door
opening.
The grille for directing exhaust air is
adjustable and is normally angled outwards to
achieve the best protection against incoming
air.
The efficiency of the air curtain depends
on the air temperature, pressure differences
across the doorway and any wind pressure.
NOTE! Negative pressure in the building
considerably reduces the efficiency of the air
curtain. The ventilation should therefore be
balanced.
Mounting
The air curtain unit is installed horizontally
with the supply air grille facing downwards
as close to the door as possible. Minimum
distance from outlet to floor for electrically
heated units is 1800 mm/70.9 inches. For
other minimum distances, see fig. 4.
Brackets and torx bit are enclosed in the
gable end packaging upon delivery.
PAEC3200C-NA
Installation and operating instructions
Mounting with wall brackets (fig. 6)
1. Mount the brackets on the wall, see fig.6A
and dimension drawing fig.1. If the wall is
uneven the brackets must be compensated
for this.
2. Hook on the unit at the lower edge of the
brackets. (Fig.6B)
3. Bend the top of the console over the the
unit and slide the units screws along the
rail into the slots on the consoles. (Fig.6C)
When the bracket is bent once, it must be
replaced if bent back more than 45 °.
4. Lock the nuts against the brackets. (Fig.6D)
Horizontal mounting on the ceiling
Threaded rods, hanging brackets and ceiling
mounting brackets for ceiling mounting are
available as accessories, see accessories pages
and separate manuals.
Electrical installation
The installation, which should be preceded
by an omnipolar/cut-off switch with a contact
separation of at least 3 mm/0.12 in, should
only be wired by a competent electrician and
in accordance with the latest edition of IEE
wiring regulations. The control system is pre-
installed in the air curtain.
Unit without heating
Connected via the built-in control board with
1.5 m/4.9 ft cord.
Unit with water heating
Connected via the built-in control board with
1.5 m/4.9 ft cord.
Unit with electrical heating
The electrical connection is made on the
top of the unit. See Fig.2. 208V3~/ 480V3~/
600V3~ power supply for heat and control*1
*2 should be connected to a terminal block in
the primary terminal box.
*1 480V3~/ 600V3~ Control supply is
transformed via internal transformer to
230V~ and routed through 2x 10A fuses in the
primary terminal box.
*2 208V3~ Control supply is connected
internally through 2x 10A fuses in the
primary terminal box.