Turn The Measuring Cell With Respect To The Housing - Siemens SITRANS P MK II Series Instruction Manual

Transmitter for pressure
Table of Contents

Advertisement

Available languages

Available languages

Instruction Manual
2.1.2

Turn the measuring cell with respect to the housing

If necessary, on the SITRANS P transmitter, the electronic housing can be twisted
with respect to the measuring cell in order to move the electronics end to the
viewing direction.
Only limited rotation is permitted!
The rotation range (7) is marked on the base of the electronic housing. On the
neck of the measuring cell there is an orientation mark (6) which must remain
within the marked range during rotation.
-
Undo the locking screw (8)
-
Turn the housing within the marked range (7)
-
Tighten the locking screw (torque 3.4
CAUTION
Observe turning range, otherwise this may cause a damage of the
internal connection of electronic and measuring cell.
SITRANS P, MK II
C73000-B5674-C100-02
+0.2
Nm)
7MF4010