1
Product Introduction
The Delta External Battery Pack is applicable to Delta Amplon RT 5/ 6/ 8/ 10/ 15/
20kVA UPS. When the UPS is operating during a power outage, the battery pack
provides DC power, which maintains inverter operation to supply power to the
critical loads connected to the UPS.
(Figure 1: Delta External Battery Pack Front View)
2
Important Safety Instructions
y
Servicing of batteries and battery packs must be performed or supervised by
qualified service personnel knowledgeable in batteries, battery packs and the
required precautions. Keep unauthorized personnel away from batteries and
battery packs.
y
A battery can present a risk of electric shock and high short-circuit current.
y
To reduce the risk of fire or electric shock, install the battery pack in a tempera-
ture and humidity controlled indoor area free of conductive contaminants.
y
Forbid opening or removing the cover of the battery pack to avoid high voltage
electric shock.
y
The risk of dangerous high voltage is possible when the batteries are still
connected to the UPS even though the UPS is disconnected from the mains.
Do not forget to disconnect the battery cable to completely cut off the battery
source.
y
Only qualified service personnel can perform battery replacement. Before
battery replacement, please turn off the battery breaker. If replacing the
batteries without turning off the UPS, please make sure the UPS has detected
"Battery Disconnected" before connecting the battery cable or turning on the
battery breaker.
y
Only use the same type of batteries from the same supplier. Never use old,
new and different Ah batteries at the same time.
y
The number of batteries must meet UPS requirements.
y
Do not reverse or short circuit the polarity + and – when connecting the batte-
ries because this will destroy the device and constitute a risk of electric shock
or fire.
y
Use a voltage meter to measure whether the total voltage, after battery pack
connection, is around 12.5Vdc × the total number of batteries.
y
The external slits and openings in the battery pack are provided for ventilation.
To ensure reliable operation of the battery pack and to protect the battery pack
from overheating, these slits and openings must not be blocked or covered. Do
not insert any object into the slits and openings that may hinder ventilation.
y
Do not allow liquid or any foreign object to enter the battery pack.
y
Do not place beverages or any other liquid-containing vessels on or near the
battery pack.
y
Do not dispose of the battery or batteries in a fire. The batteries may explode.
y
Do not open or mutilate the battery or batteries. The released electrolyte is
harmful to the skin and eyes and may be toxic.
www.deltapowersolutions.com
y
Observe the following before replacing batteries:
1. Remove watches, rings, or other metal objects.
2. Use tools with insulated handles.
3. Wear rubber gloves and boots.
4. Do not lay tools or metal parts on the top of batteries.
5. Disconnect charging source prior to connecting or disconnecting the
batteries' terminals.
3
Package List
2
Delta UPS - Amplon Family
Delta External Battery Pack for
Amplon RT 5/ 6/ 8/ 10/ 15/ 20kVA UPS
Installation & Operation Quick Guide
ENGLISH
6
7
× 3
No.
1
Delta External Battery Pack
2
Installation & Operation Quick Guide
3
Bracket Ear
4
Battery Cable
5
Tower Stand Extender
6
M4 Screw
7
Cable Tie
8
Cable Ties Fixing Holder
4
Installation Procedures
y
Rack Mounting:
1
Attach the included bracket ears to the lateral mounting holes of the Delta
external battery pack. See Figure 2.
5013271102
1
3
4
5
× 4
× 4
× 2
× 4
× 4
× 4
8
× 3
× 3
Item
Q'ty
1 PC
1 PC
1 SET
1 SET
RT-6KB: 4 PCS
RT-10KB: 6 PCS
3 PCS
3 PCS
3 PCS
(Figure 2: Mount the Bracket Ears)
1 / 4
2
Follow steps
1
to
4
to install the Delta external battery pack in Delta's
rail kit (optional). See Figure 3.
Step
1
: Adjust the length of the rails according to your rack.
Step
2
: Tighten the rails' nuts.
Step
3
: Fix the rails on your rack.
Step
4
: Install the Delta external battery pack on your rack and
tighten the provided screws.
3
4
(Figure 3: Install the Delta External Battery Pack on Your Rack)
NOTE:
1. If you want to use a non-Delta rail kit, please only follow step
4
.
2. If you want to use a non-Delta rail kit, the minimum distance
for the Delta external battery pack supported on non-Delta rail kit
is at least 40mm.
3
To eliminate the battery cable bending space, please use the M4
screws, the cable tie and the cable ties fixing holder (provided in the
external battery pack's package) to fix the battery cable, so as to prevent
interference between the battery cable and the panel of the Rack. The
installation steps are as following. The Delta external battery pack has
two models, RT-6KB and RT-10KB. The two models' fixing methods are
similar. Thus, in Figure 4 & Figure 5, only the illustration of model RT-6KB
and 5/ 6kVA UPS is taken for example.
Step 1:
Use the M4 screws (provided in the external battery pack's
package) to fix cable ties fixing holder (provided in the external
battery pack's package) on the hole of the rear panel.
See Figure 4.
Delta Amplon RT 5/ 6kVA UPS
V
TMO
接口
232
RS-
RS-
485
远程
紧急
关机
干接
P3
P4
P2
P1
并联
接口
PUT
OUT
并联
接口
连接
外接
V DC
电池
50A
192
断路
V DC
63A
250
Delta External Battery Pack
连接
电池
V DC
50A
外接
192
(RT-6KB Model)
(Figure 4: Fix the Cable Ties Fixing Holder)
Continue to the Next Page

3
1
2
INP
UT
Cable Ties
× 1
Fixing Holder
M4 Screw
× 1

Advertisement

loading

Summary of Contents for Delta Amplon Series

  • Page 1 ENGLISH Product Introduction The Delta External Battery Pack is applicable to Delta Amplon RT 5/ 6/ 8/ 10/ 15/ 20kVA UPS. When the UPS is operating during a power outage, the battery pack provides DC power, which maintains inverter operation to supply power to the critical loads connected to the UPS.
  • Page 2 192V (RT-6KB Model) NOTE: There are two identical external battery connectors ( & ) on the Delta external battery pack, and you may use either of the battery connectors ( & ) to connect to the UPS. (Figure 5: Fix the Battery Cable)
  • Page 3 外 15/ 20kVA UPS to the 15/ 20kVA UPS. The Delta external battery pack has two models, RT- 6KB and RT-10KB. The two models’ parallel methods and UPS connection methods are similar. Thus, in the following instructions and Figure 16, each of the two parallel 15/ 20kVA UPSs connecting to two parallel Delta external 孔...
  • Page 4 E ups.australia@deltaww.com Operation Procedures Thailand Follow Delta Amplon RT Series 5/ 6/ 8/ 10kVA UPS User Manual & Delta Delta Electronics (Thailand) Public Co.,Ltd. Amplon RT Series 15/ 20kVA UPS User Manual to execute input/ output 909 Soi 9, Moo 4, E.P.Z., Bangpoo Industrial Estate, Tambon Prakasa, Amphur Muang-samutprakarn, Samutprakarn Province 10280, Thailand connection.

This manual is also suitable for:

Rt-6kbRt-10kb