External battery pack
Hide thumbs Also See for Amplon Series:

Advertisement

Step 2
After use the battery cable to connect the UPS and the
external battery pack, please use the cable ties to fix the
battery cable on the cable ties fixing holder.
Delta Amplon RT 5/ 6kVA UPS
接口
32
RS-2
RS-4
85
远程紧
关机
P4
干接点
P2
P3
P1
并联接
并联接
外接电
192V
断路器
DC
63A
250V
Delta External Battery Pack
池连
接孔
50A
外接电
192V
DC
(RT-6KB Model)
(Figure 5: Fix the Battery Cable)
y
Tower Mounting:
1
Connect the provided tower stand extenders with the tower stands
provided in the UPS's carton (please take the UPS and the Delta external
battery pack's size into consideration). See Figure 6.
Tower Stand Extender
Tower Stands
(Figure 6: Connect the Tower Stand Extenders
with the UPS's Tower Stands)
2
Pull out the Delta external battery pack's control panel (
it 90° clockwise (
3
) and re-insert the control panel (
rotate the Delta logo nameplate 90° clockwise (
5
Rotate 90°
2
1
3
(Figure 7: Rotate the Delta External Battery Pack's
Control Panel & Delta Logo Nameplate)
3
Carefully lift the Delta external battery pack upright with the Delta logo
and the icon shown on the control panel facing up. A minimum of
two people are required. See Figure 8.
www.deltapowersolutions.com
See Figure 5.
V
TMO
INPU
T
PUT
OUT
Cable Ties
× 1
池连接
50A
DC
4
1
2
&
), rotate
4
). After that,
). See Figure 7.
5
(Figure 9: Place the Delta External Battery Pack and the UPS inside
y
Connect the Delta External Battery Pack with the 5/ 6/ 8/ 10kVA UPS
The Delta external battery pack has two models, RT-6KB and RT-10KB. The two
models' paralleling methods and UPS connection methods are similar. Thus, in
Figure 10, only the illustration of model RT-6KB and 5/ 6kVA UPS is taken for
example.
4
1
90°
(Figure 8: Place the Delta External Battery Pack Upright)
Place the Delta external battery pack and the UPS inside the tower
stands. See Figure 9.
UPS
Delta External Battery Pack
the Tower Stands)
Connect one end of the provided battery cable (
battery connector (
4
) on the UPS, and connect the other end to the
external battery connector (
7
) on the Delta external battery pack. Use
the provided screws (
2
) and standoffs (
3
) to fix the battery cable
firmly. Make sure that the positive cable (+) connects to the positive pole
(+) and the negative cable (-) connects to the negative pole (-). See
Figure 10.
2 / 4
Delta Amplon RT 5/ 6kVA UPS
Delta External Battery Pack
(RT-6KB Model)
NOTE: There are two identical external battery connectors (
) on the Delta external battery pack, and you may use either of the
battery connectors (
y
Connect the Delta External Battery Pack with the 15/ 20kVA UPS
NOTE: If it is not for common battery application, each 15/ 20kVA UPS
must connect to at least two external battery packs, and the number of
battery packs must be the multiple of two and only two of the battery
packs need to be connected to the 15/ 20kVA UPS. The Delta external
battery pack has two models, RT-6KB and RT-10KB. The two models'
parallel methods and UPS connection methods are similar. Thus, in
the following instructions and Figure 13, only one 15/ 20kVA UPS
connecting to two Delta external battery packs (model RT-10KB) is
taken for example.
1
Remove the two knockout covers from the UPS's rear panel, and install
two cable glands (user-supplied) on the location where you removed the
knockout covers. See Figure 11.
2
Insert the two battery cables (provided in the UPS's package) into the
two user-supplied cable glands, connect the battery cables to the UPS's
1
) to the external
battery input terminals, and turn the cable glands in a clockwise direction
in order to fix the cable glands on the UPS firmly. See Figure 12.
Continue to the Next Page
4
TM
OV
3
2 接口
-23
RS
UT
INP
UT
TP
OU
TMOV
2 接口
5
RS-23
RS-48
INPUT
远程紧
关机
干接点
P4
P3
P1
P2
并联接
OUTP
UT
并联接
7
池连接
50A
外接电
192V
DC
断路器
63A
连接
250V
DC
电池
50A
6
外接
1 92V
DC
外接电
池连接
DC
50A
192V
5
8
1
(Figure 10)
7
&
7
&
8
) to connect to the UPS.
15/ 20kVA UPS
Knockout Covers
Cable Glands
(Figure 11)
15/ 20kVA UPS
(Figure 12)

8