123electric Smart BMS gen 3 Manual page 16

Table of Contents

Advertisement

V balance: This is the balancing voltage where
you want all the cells to end up. Above this
voltage the cell modules start to dissipate 1
ampere to balance the cells. This setting can
be changed with the option switches on the
Begin Board.
T min: If one of the cells gets below this
minimum cell temperature threshold the "Tl"
warning indicator on the battery details
screen is switched on. Both relays to control
external devices will be switched off.
T max: If one of the cells gets above this
maximum cell temperature threshold the
"Th" warning indicator on the battery details
screen is switched on. Both relays to control
external devices be switched off.
123electric
The Netherlands
E-mail: info@123electric.eu
www.123electric.eu
Charge restart: The charge relay switches ON
again if the capacity is below the
programmable "Charge restart" and the BMS
is in "Normal mode". This is to prevent
toggling relays.
Discharge restart: The load relay will be
switched on again if the capacity is above the
programmable "Discharge restart" and the
BMS is in "Normal mode".
Prevent auto-lock: Enabling this function
prevent the device goes into sleep mode.
Show simulator: If you don't have an
123\SmartBMS but you like to discover the
App, you can run a simulator.
Support: You can contact the app developer
and give your feedback. The App version will
be showed here.
16