5.3

PARAMETER CONFIGURATION 2

Group
Parameter Description
rEG
SEt
Set Point
rEG
LS
Minimum Set point
rEG
US
Maximum Set point
Compressor regulation differential in
rEG
HY
normal mode
Compressor regulation differential in
rEG
HYE
energy saving mode
rEG
odS
Output activation delay at start-up
rEG
AC
Anti-short cycle delay
Regulation percentage=F(P1; P2)
rEG
rtr
(100=P1; 0=P2)
rEG
CCt
Maximum duration for Pull Down
Pull Down phase differential (SET+CCS or
rEG
CCS
SET+HES+CCS)
Threshold for automatic activation of Pull
rEG
oHt
Down in normal mode (SET+HY+oHt)
Threshold for automatic activation of Pull
rEG
oHE
Down in energy saving mode
(SET+HES+HYE+oHE)
rEG
Con
Compressor ON time with faulty probe
rEG
CoF
Compressor OFF time with faulty probe
Prb
P1C
Probe P1 selection
Prb
P2C
Probe P2 selection
Prb
P3C
Probe P3 selection
Prb
P4C
Probe P4 selection
Prb
ot
Probe P1 calibration
Prb
P2P
Probe P2 presence
Prb
oE
Probe P2 calibration
Prb
P3P
Probe P3 presence
Prb
o3
Probe P3 calibration
Prb
P4P
Probe P4 presence
Prb
o4
Probe P4 calibration
Variable Speed Compressor Differential in
VSC
HY1
normal mode
Variable Speed Compressor Differential in
VSC
HYS
energy saving mode
Minimum value for Variable Speed
VSC
FMi
Compressor (RPM * 10)
Maximum value for Variable Speed
VSC
FMA
Compressor (RPM * 10)
Value when Variable Speed Compressor is
VSC
Fr0
shut-down
VSC
tSt
PI regulator: temperature sampling time
VSC
iSt
PI regulator: integral sampling time
VSC
vdC
Type of Variable Speed Drive
Signal output variation for Variable Speed
VSC
voS
Compressor (SET-HY≤T≤SET+HY)
1592040010 XRi30-31T EN v1.2 2020.08.26
Value
Protected U.O.M.
38.0
Pr1
°F
-148.0
Pr1
°F
302.0
Pr1
°F
6.0
Pr1
°F
6.0
Pr1
°F
0
Pr1
min
0
Pr1
min
100
Pr2
00:00
Pr2
hh:mm
0.0
Pr2
°F
20.0
Pr2
°F
20.0
Pr2
°F
10
Pr1
min
15
Pr1
min
ntC
Pr2
ntC
Pr2
ntC
Pr2
ntC
Pr2
0
Pr1
°F
Y
Pr1
0
Pr1
°F
no
Pr1
0
Pr1
°F
no
Pr1
0
Pr1
°F
4.0
Pr2
°C
4.0
Pr2
°C
198
Pr2
RPM*10
450
Pr2
RPM*10
90
Pr2
RPM*10
00:10
Pr2
hh:mm
01:00
Pr2
hh:mm
FrE
Pr2
1
Pr2
Hz
XRi30T-XRi31T
Range
LS to US
[-100.0°C to SET]
[-148.0°F to SET]
[SET to 150.0°C]
[SET to 302.0°F]
[0.1°C to 25.0°C]
[0.1°F to 45.0°F]
[0.1°C to 25.0°C]
[0.1°F to 45.0°F]
0 to 255 min
0 to 50 min
0 to 100
0 to 23h50min
[-12.0°C to 12.0°C]
[-21.6°F to 21.6°F]
[0.0°C to 25.0°C]
[0.0°F to 45.0°F]
[0.0°C to 25.0°C]
[0.0°F to 45.0°F]
0 to 255 min
0 to 255 min
ntC; PtC; Pt1
ntC; PtC; Pt1
ntC; PtC; Pt1
ntC; PtC; Pt1
[-12.0°C to 12.0°C]
[-21.6°F to 21.6°F]
n(0); Y(1)
[-12.0°C to 12.0°C]
[-21.6°F to 21.6°F]
n(0); Y(1)
[-12.0°C to 12.0°C]
[-21.6°F to 21.6°F]
n(0); Y(1)
[-12.0°C to 12.0°C]
[-21.6°F to 21.6°F]
[0.1 to 25.5°C]
[0.11 to 45.0°F]
[0.1 to 25.5°C]
[0.1 to 45.0°F]
0 to FMA
FMi to 500
0 to 200
00:00 to 42m:30s
00:00 to 42m:30s
nu(0); FrE(1)
StP; 1 to 255Hz
27/42