Electrical connection
6.6 Connecting the converter
Machine overheating
Operating explosion-protected machines at the converter without using the appropriate
protective equipment can result in death or severe injury.
Always use PTC thermistor monitoring when operating explosion-protected machines at the
converter. Tripping units according to Directive 2014/34/EU ("Explosion Protection
Directive") are always necessary when using PTC thermistor monitoring.
Machines with non-sparking "ec" "nA" type of protection
The operation of the explosion-proof machines on the converters is permitted, when the
specifications for the speed control range and torque characteristic are observed, and if
winding temperature monitoring is ensured via the integrated temperature sensors in
conjunction with a certified tripping unit.
Machines with increased safety "e" or "eb" type of protection
Converter operation for these machines must be expressly certified. It is crucial that you
carefully observe the specific manufacturer's information and instructions. Converter and
protective devices must be marked as belonging together and the permitted operating data
must be defined in the common EC-type examination certificate.
Machines with type of protection, dust explosion protection "tb" or dust explosion protection
"tc"
These machines are generally equipped with 3 PTC thermistors in accordance with DIN
44082 with a rated response temperature that depends on the maximum possible surface
temperature. Select the PTC thermistors in accordance with this standard. If the temperature
of the cable glands is not stamped on the rating plate, then it is max. 70 °C. Use suitable
cables for this temperature. Do not exceed the maximum frequency dependent on the
number of poles, which is stamped on the rating plate.
System, converter - cable - electrical machine
Carefully comply with the information and data provided in EN / IEC 60034-17 and
EN / IEC 60034-25 regarding winding stress. For line supplies with operating voltages up to
690 V, the maximum value of the voltage peaks at the end of the cable must not exceed
twice the value of the converter's DC-link voltage.
See also
Thermal protection (Page 43)
86
WARNING
1MB..1/2/3/4 - shaft heights 63 ... 355
Operating Instructions, 06/2020, A5E44455710A