Insulated Bearings For Converter Operation - Siemens SIMOTICS XP Series Operating Instructions Manual

Low-voltage motors
Table of Contents

Advertisement

Preparing for use
4.14 Converter operation
4.14.4

Insulated bearings for converter operation

If the machine is controlled from a low-voltage converter, depending on the machine type, an
insulated bearing can be fitted at the NDE.
An insulated speed encoder can be optionally mounted.
Comply with the information provided on the machine plates relating to bearing insulation
and possible jumpers.
Figure 4-2
NOTICE
Bearing damage
The bearing insulation must not be bridged. Bearing currents can damage bearings.
• Do not bridge the bearing insulation for subsequent installation work, such as the
• Where necessary, contact the Service Center.
If you connect 2 motors in series in "tandem operation", install an insulated coupling between
the motors.
Figure 4-3
50
Driven machine
Motor
Coupling
Schematic representation of a single drive
installation of an automatic lubrication system or a non-insulated vibration sensor.
Driven machine
Motor
Coupling
Schematic representation of a tandem drive
Insulated bearings
Insulated tachometer fitting
Insulated bearings
Insulated tachometer fitting
Insulated coupling
1MB..1/2/3/4 - shaft heights 63 ... 355
Operating Instructions, 06/2020, A5E44455710A