S-15A Resistance Check (5 Ton Only); S-15B Capacitance Check (5 Ton Only); Checking Compressor - Amana AVZC20 Series Service Instructions Manual

Inverter heat pump condenser units with r-410a refrigerant blowers, coils, & accessories
Hide thumbs Also See for AVZC20 Series:
Table of Contents

Advertisement

SERVICING

S-15A RESISTANCE CHECK (5 TON ONLY)

HIGH VOLTAGE !
D
ALL
ISCONNECT
POWER BEFORE SERVICING OR
. M
INSTALLING
ULTIPLE POWER SOURCES MAY BE
. F
PRESENT
AILURE TO DO SO MAY CAUSE PROPERTY
,
DAMAGE
PERSONAL INJURY OR DEATH
1. Discharge capacitor and remove wire leads.
D
ISCHARGE CAPACITOR THROUGH A
.
HANDLING
OHMMETER
TESTING CAPACITOR RESISTANCE
2. Set an ohmmeter on its highest ohm scale and connect the
leads to the capacitor -
A. Good Condition - indicator swings to zero and slowly re-
turns to infinity. (Start capacitor with bleed resistor will not
return to infinity. It will still read the resistance of the resis-
tor).
B. Shorted - indicator swings to zero and stops there - replace.
C. Open - no reading - replace. (Start capacitor would read
resistor resistance.)

S-15B CAPACITANCE CHECK (5 TON ONLY)

Using a hookup as shown below, take the amperage and voltage
readings and use them in the formula:
Capacitance (MFD) = 2650 X Amperage
D
ISCHARGE CAPACITOR THROUGH A
.
HANDLING
WARNING
.
WARNING
20
30 OHM
TO
RESISTOR BEFORE
CAPACITOR
Voltage
WARNING
20
30 OHM
TO
RESISTOR BEFORE
VOLTMETER
AMMETER
TESTING CAPACITANCE
S-17 CHECKING COMPRESSOR
WARNING
Hermetic compressor electrical terminal venting can
be dangerous. When insulating material which
supports a hermetic compressor or electrical terminal
suddenly disintegrates due to physical abuse or as a
result of an electrical short between the terminal and
the compressor housing, the terminal may be
expelled, venting the vapor and liquid contents of the
compressor housing and system.
If the compressor terminal PROTECTIVE COVER and gasket (if re-
quired) are not properly in place and secured, there is a remote
possibility if a terminal vents, that the vaporous and liquid dis-
charge can be ignited, spouting flames several feet, causing po-
tentially severe or fatal injury to anyone in its path.
This discharge can be ignited external to the compressor if the
terminal cover is not properly in place and if the discharge im-
pinges on a sufficient heat source.
Ignition of the discharge can also occur at the venting terminal or
inside the compressor, if there is sufficient contaminant air present
in the system and an electrical arc occurs as the terminal vents.
Ignition cannot occur at the venting terminal without the pres-
ence of contaminant air, and cannot occur externally from the
venting terminal without the presence of an external ignition
source.
Therefore, proper evacuation of a hermetic system is essential at
the time of manufacture and during servicing.
To reduce the possibility of external ignition, all open flame, elec-
trical power, and other heat sources should be extinguished or
turned off prior to servicing a system.
S-17A Resistance Test
The Inverter on the outdoor control board takes the position sig-
nal from the UVW line, connected with the compressor. If the
system detects a malfunction on the compressor, check the insu-
lation resistance in accordance with the following procedure.
15 AMP
FUSE
CAPACITOR
43