Checking Voltage; Checking Wiring; Checking Thermostat And Wiring; S-3A Thermostat And Wiring - Amana AVZC20 Series Service Instructions Manual

Inverter heat pump condenser units with r-410a refrigerant blowers, coils, & accessories
Hide thumbs Also See for AVZC20 Series:
Table of Contents

Advertisement

SERVICING
S-1 CHECKING VOLTAGE
1. Remove outer case, control panel cover, etc., from unit being
tested.
With power ON:
L
V
INE
OLTAGE NOW PRESENT
2. Using a voltmeter, measure the voltage across terminals L1
and L2 of the contactor for the heat pump condenser unit or
at the field connections for the air handler or heaters.
ComfortNet
TM
Ready Heat Pump Condenser Units: Measure
the voltage across the L1 and L2 lugs on the unitary (UC)
control.
3. No reading - indicates open wiring, open fuse(s) no power or
etc., from unit to fused disconnect service. Repair as needed.
4. With ample voltage at line voltage connectors, energize the
unit.
Unit Supply Voltage
Voltage
208/230
NOTE: When operating electric heaters on voltages other than
240 volt, refer to the System Operation section on electric heat-
ers to calculate temperature rise and air flow. Low voltage may
cause insufficient heating.
S-2 CHECKING WIRING
HIGH VOLTAGE !
D
ALL
ISCONNECT
POWER BEFORE SERVICING OR
. M
INSTALLING
ULTIPLE POWER SOURCES MAY BE
. F
PRESENT
AILURE TO DO SO MAY CAUSE PROPERTY
,
DAMAGE
PERSONAL INJURY OR DEATH
1. Check wiring visually for signs of overheating, damaged in-
sulation and loose connections.
2. Use an ohmmeter to check continuity of any suspected open
wires.
3. If any wires must be replaced, replace with comparable gauge
and insulation thickness.
WARNING
.
Min.
Max
197
253
WARNING
.
S-3 CHECKING THERMOSTAT AND WIRING
ComfortNet™ Ready Models
Communicating Thermostat Wiring: The maximum wire length
for 18 AWG thermostat wire is 250 feet.

S-3A THERMOSTAT AND WIRING

L
V
.
INE
OLTAGE NOW PRESENT
With power ON, thermostat calling for cooling/heating.
1. Use a voltmeter to check for 24 volt at thermostat wires C and
R in the indoor unit control panel.
2. No voltage indicates trouble in the thermostat, wiring or trans-
former source.
3. Check the continuity of the thermostat and wiring. Repair or
replace as necessary.
With power ON:
WARNING
L
V
.
INE
OLTAGE NOW PRESENT
Resistance Heaters
1. Set room thermostat to a higher setting than room tempera-
ture so both stages call for heat.
2. With voltmeter, check for 24 volt at each heater relay.
3. No voltage indicates the trouble is in the thermostat or wir-
ing.
4. Check the continuity of the thermostat and wiring. Repair or
replace as necessary.
NOTE: Consideration must be given to how the heaters are wired
(O.D.T. and etc.). Also safety devices must be checked for continu-
ity.
WARNING
21