Download Print this page
System Sensor DH400ACDCIHT Installation And Maintenance Instructions Manual
System Sensor DH400ACDCIHT Installation And Maintenance Instructions Manual

System Sensor DH400ACDCIHT Installation And Maintenance Instructions Manual

Advertisement

Quick Links

INSTALLATION AND MAINTENANCE INSTRUCTIONS
DH400ACDCIHT Air Duct Smoke Detector
Before Installing
Please thoroughly read the System Sensor Guide for Proper
Use of Smoke Detectors in Duct Applications (A05-1004),
which provides detailed information on detector spacing,
placement, zoning, wiring, and special applications. Copies
of this manual are available online at www.systemsensor.com
or via System Sensor's toll free fax-back service, Documents
on Demand at 800/736-7672. NFPA Standards 72 and 90A
should also be referenced for detailed information.
NOTICE: This manual should be left with the owner/user
of this equipment.
IMPORTANT: This detector must be tested and maintained
regularly following NFPA 72 requirements. The detector
should be cleaned at least once a year.
This detector is intended for use only with the 1451DHHT
detector head (supplied).

Table of Contents

[1]
General Description
[2]
[3]
[4]
[5]
[6]
[7]
[8]
List of Tables and Figures
Fig. 1: Duct Detector Exploded View
Fig. 2: Installation of Sampling Tube Gaskets
Fig. 3: Mounting Location of Speed Nuts
Table 1: Inlet Sampling Tube Selection
Fig. 4: Inlet Sampling Tube
Fig. 5: Sampling Tube Mounting Configurations
Fig. 6: Sampling Tube Filter Installation
Fig. 7: Wiring Diagram
Fig. 8: Wiring Diagram - No Control Panel
Fig. 9: Wiring Diagram - Accessories
Fig. 10: Testing Detector Alarm
Fig. 11: Detector Head Removal
Fig. 12: RTS451/RTS451KEY Test Coil Installation
Fig. 13: Ion Head Exploded View
D400-64-00
WARNING
[1] General Description
An HVAC system supplies conditioned air to virtually every
area of a building. Smoke introduced into this air duct sys-
tem will be distributed to the entire building. Smoke detec-
tors designed for use in air duct systems are used to sense
the presence of smoke in the duct.
Model DH400ACDCIHT Air Duct Smoke Detectors are sup-
plied with the model 1451DHHT ionization detector head.
This smoke detection method is combined with an efficient
housing design that samples air passing through a duct
and allows detection of a developing hazardous condition.
When sufficient smoke is sensed, an alarm signal is initi-
ated at the fire control panel monitoring the detector, and
appropriate action can be taken to shut off fans and blow-
ers, change over air handling systems, etc. These actions
can facilitate the management of toxic smoke and fire gases
throughout the areas served by the duct system.
The DH400ACDCIHT air duct smoke detector is designed to
operate from 24 VDC, 24 VAC, 120 VAC, or 240 VAC. Alarm
Page
and supervisory relay contacts are available for control
1
panel interface (alarm initiation), HVAC control, and other
2
auxiliary functions. This detector is not designed for 2-wire
2
applications.
2
8
For testing, the alarm can be enabled by a magnet activated
9
test switch or by the optional remote test station. The duct
10
smoke detectors latch into alarm state when alarm occurs.
11
LEDs on each detector illuminate to provide local alarm
12
indication, and optional accessories offer a variety of
annunciation capabilities.
Page
2
The detector can be reset by a momentary power inter-
3
ruption, by the magnet activated reset switch, or by the
3
optional remote test station.
3
4
NOTICE: The DH400ACDCIHT can be installed outdoors
4
using the optional accessory DH400 OE-1.
5
Please refer to section 9 for a description and
6
installation instructions.
7
8
9
9
10
10
1
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
www.systemsensor.com
I56-991-08R

Advertisement

loading
Need help?

Need help?

Do you have a question about the DH400ACDCIHT and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for System Sensor DH400ACDCIHT

  • Page 1: Table Of Contents

    This detector is intended for use only with the 1451DHHT detector head (supplied). The DH400ACDCIHT air duct smoke detector is designed to operate from 24 VDC, 24 VAC, 120 VAC, or 240 VAC. Alarm Table of Contents...
  • Page 2: Exploded View Of Duct Detector Components

    10. One inlet tube end plug [4.1] Verify Duct Air Flow Direction And Velocity 11. Two #10 speed nuts Model DH400ACDCIHT detectors are designed to be used 12. One test coil and parts bag in air handling systems having air velocities of 500 to 4000 feet per minute.
  • Page 3 [4.3] Secure The Detector Housing To The Duct Mounting the detector housing in a vertical orientation Remove the duct housing cover. Slide the foam gaskets over is acceptable, provided that the air flows directly into the the tube bushings as shown in Figure 2. Make sure the two sampling tube holes as indicated in Figure 4.
  • Page 4 Figure 4. Air duct detector inlet sampling tube: AIR HOLES SAMPLING FLANGE TUBE END CAP ARROW AIR FLOW DIRECTION MUST FACE INTO AIR FLOW H0108-02 Figure 5. Tube mounting configurations with varying air flow direction: DOTS INDICATE POSITION OF SAMPLING TUBE HOLES AIR FLOW AIR FLOW DIRECTION...
  • Page 5 Replacement filters can be ordered on the conduit holes in the housing. Solid conduit connec- from System Sensor, 3825 Ohio Ave., St. Charles, IL 60174. tions may be used, if desired. (Exhaust tube/intake tube filter P/N F36-05-00).
  • Page 6 Figure 7. System wiring diagram for duct detectors using a UL listed control panel (see Figure 8 for wiring of optional accessories): CAUTION Do not loop wire under terminals when wiring detectors. Break wire runs to provide system supervision of connections. H0240-00 D400-64-00 I56-991-08R...
  • Page 7 TROUBLE IS REMOVED, AND DURING RESET. OPEN CONTACTS CONTACTS EXTINGUISH OPTIONAL APA451 GREEN “POWER” LED POWER TO INDICATE TROUBLE CONDITION. DH400ACDCIHT APA451 DUCT DETECTOR AUDIBLE PIEZO ALERT WITH ALARM AND POWER (TROUBLE) LEDS. FOR STAND ALONE APPLICATIONS ONLY. APA451 RECOMMENDED FOR COMPLIANCE TO NFPA 90A.
  • Page 8: Duct Detector Maintenance And Test Procedures

    Figure 9. Wiring diagrams for optional accessories (see Figure 7 for APA451 wiring diagram): ALARM SIGNAL (+) ALARM SIGNAL (+) ALARM SIGNAL (+) AUX POWER (–) AUX POWER (–) AUX POWER (–) (–) (–) FIELD INSTALLED DUCT DETECTOR PA400 (OPTIONAL) DUCT DETECTOR RA400Z (OPTIONAL) JUMPER...
  • Page 9: Detector Cleaning Procedures

    RTS451/RTS451KEY manual. The DH400ACDCIHT duct detector can be reset by the RTS451/RTS451KEY. If [6.1] Air Filters a system control panel is used, the panel itself may also 1.
  • Page 10: Specifications

    4. Notify the proper authorities testing has been completed and the smoke detector system is back in operation. [8] Model DH400ACDCIHT Air Duct Smoke Detector Specifications Description HVAC air duct mounted ionization smoke detector for separately powered systems or stand alone systems. Auxiliary alarm relay contacts provide fan contactor shutdown to prevent HVAC circulation of smoke.
  • Page 11: Dh400 Oe-1 Description And Installation

    Locate the two adhesive backed gaskets packaged with the The DH400 OE-1 all-weather enclosure is specifically enclosure. designed to house and protect the System Sensor model DH400ACDCIHT high temperature duct detector from the NOTE: In order to provide effective sealing, these gaskets elements.
  • Page 12: Warranty

    St. Charles, IL 60174. Please include a note describing the malfunction and for a period of three years from date of manufacture. System Sensor makes suspected cause of failure. The Company shall not be obligated to repair no other express warranty for this air duct smoke detector.