Air duct smoke detector with extended air speed range

Advertisement

INSTALLATION AND MAINTENANCE INSTRUCTIONS
DH100LP Air Duct Smoke Detector
with Extended Air Speed Range
The Innovair DH100LP model is a photoelectric detector
approved for an extended air speed range of 100 to 4000
feet per minute (0.5 m/s to 20.3 m/s) and has an opera-
tional temperature range of 32°F to 131°F (0°C to 55°C).
Before Installing
Please thoroughly read the System Sensor Guide for Proper
Use of Smoke Detectors in Duct Applications (A05-1004),
which provides detailed information on detector spacing,
placement, zoning, wiring, and special applications. Copies
of this manual are available online at www.systemsensor.com
or via System Sensor's toll free fax-back service, Documents
on Demand at 800/736-7672. NFPA Standards 72 and 90A
should also be referenced for detailed information.
NOTICE: This manual shall be left with the owner/user of
this equipment.
IMPORTANT: This detector must be tested and maintained
regularly following NFPA 72 requirements. The detector
should be cleaned at least once a year.

Table of Contents

[1] General Description ................................................... 1
[2] Limitations of Duct Smoke Detectors........................... 1
[5] Installation Sequence .................................................. 2
and Test Procedures .................................................... 5
[7] Detector Cleaning Procedures...................................... 7
[8] Board Replacement ..................................................... 7
[9] Specifications.............................................................. 8
Warranty........................................................................... 8

[1] General Description

An HVAC system supplies conditioned air to virtually every
area of a building. Smoke introduced into this air duct
system will be distributed throughout the entire building.
Smoke detectors designed for use in air duct systems are
used to sense the presence of smoke in the duct.
Model DH100LP Air Duct Smoke Detectors utilizes photo-
electric technology for the detection of smoke. This detec-
tion method when combined with an efficient housing
design samples air passing through the duct and allows
detection of a developing hazardous condition. When suf-
ficient smoke is sensed, an alarm signal is initiated at the
fire control panel monitoring the detector, and appropriate
D200-15-00
action can be taken to shut off fans, blowers, change over
air handling systems, etc. These actions can facilitate the
management of toxic smoke and fire gases throughout the
areas served by the duct system.
DH100LP detectors are designed to operate with 12/24VDC
UL listed compatible 2-wire control panels. Alarm current
must be limited to 130mA or less by the control panel.
Auxiliary relay contacts for control purposes are not avail-
able for use with the DH100LP. Control must initiate from
the control panel.
For testing, the alarm can be enabled by a magnet activated
test switch or by the optional remote test station. The duct
smoke detector latches into alarm state when an alarm
occurs. A green LED flashes to indicate power, a red LED
signals local alarm indication, and optional accessories
offer a variety of annunciation capabilities.
The DH100LP can be reset by a momentary power interrup-
tion, the reset button on the front cover, the control panel,
Page
or remote reset accessory.

[2] Limitations Of Duct Smoke Detectors

The National Fire Protection Association has established
that DUCT DETECTORS MUST NOT BE USED AS A
SUBSTITUTE FOR OPEN AREA DETECTOR PROTECTION
as a means of providing life safety. Nor are they a substi-
tute for early warning in a building's regular fire detection
system.
System Sensor supports this position and strongly recom-
mends that the user read NFPA Standards 90A, 72, and 101.
The DH100LP Air Duct Smoke Detectors are listed per UL
268A.
This device will not operate without electrical power.
Fire situations may cause an interruption of power. The
system safeguards should be discussed with your local fire
protection specialist.
This device will not sense smoke unless the ventilation
system is operating and the cover is installed.
1
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
WARNING
WARNING
WARNING
I56-0083-07R

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the INNOVAIR DH100LP and is the answer not in the manual?

Questions and answers

Summary of Contents for System Sensor INNOVAIR DH100LP

  • Page 1 Before Installing DH100LP detectors are designed to operate with 12/24VDC Please thoroughly read the System Sensor Guide for Proper UL listed compatible 2-wire control panels. Alarm current Use of Smoke Detectors in Duct Applications (A05-1004), must be limited to 130mA or less by the control panel.
  • Page 2 [3] Figure 1: Exploded View Of Duct Detector Components FOAM GASKETS CONDUIT HOLES DETECTOR SAMPLING TUBE HOUSING FILTERS PLASTIC TERMINAL STRIP SAMPLING TUBE POWER BOARD PLASTIC SAMPLING TUBE SELF-TAPPING SCREW COVER MOUNTING SCREWS DETECTOR BOARD DETECTOR COVER [5.2] Drill The Mounting Holes WARNING Remove the paper backing from the mounting template For this detector to function properly, it MUST be installed...
  • Page 3 [5.3] Secure The Detector Housing To The Duct the inlet hole on the opposite side of the duct to allow for Slide the foam gaskets over the tube bushings as shown in moisture drainage. If the tube is shorter than the width of Figure 3.
  • Page 4 Replacement filters can be ordered After the installation, use electrical tape to close from System Sensor, 3825 Ohio Ave., St. Charles, IL 60174. off some of the sampling holes so that there are a (Exhaust tube/intake tube filter P/N F36-09-11) total of 10 to 12 holes spaced as evenly as possible across the width of the duct.
  • Page 5 For signal wiring, (the wiring between interconnected service. Disable the zone or system under test to prevent detectors or from detectors to auxiliary devices), it is usu- unwanted alarms. ally recommended that single conductor wire be no smaller [6.1] Smoke Entry Tests than 18 gauge.
  • Page 6 [6.1.5] Filter Replacement the duct smoke detector housing, and the LOW side of the transmitter to the exhaust tube of the duct smoke detec- The filters do not substantially affect smoke performance tor housing. Measure and record the voltage drop across even when up to 90% of the filter is clogged.
  • Page 7 Test — The trouble condition can be caused inten- If test module readings indicate that the detector head is tionally to verify correct operation of the sys- outside of the acceptable range that is printed on the label tem. Remove the detector board to cause a of the detector, the detector requires cleaning per Section trouble condition locally and at the system [7] of this manual.
  • Page 8 The Company shall not be obli- vice for a period of three years from date of manufacture. System Sensor gated to repair or replace units which are found to be defective because makes no other express warranty for this air duct smoke detector.