TECHNICAL SPECIFICATION

Size:
Degree of protection:
Weight:
Supply Voltage:
Rated Insulation Voltage:
Conditional Short Circuit current: I
I
t (fuse rating)
2
(Triac rating)
Controlled supply:
Input Connections (mains):
(control):
Earthing system:
Analogue input impedance:
Control voltage:
Maximum load per channel:
(2.3kVA corresponds to a resistive load of 2300 Watts or an
inductive load of approximately 1750 Watts, depending on power
factor.)
Output Connections:
Maximum total load:
Fuses:
Part code:
(HBC means 'high breaking capacity' - a HBC fuse has a ceramic
case.)
Triacs:
Type:
Part code:
215 x 205 x 45 mm
IP30
2.1 kg
230 V ˜ 50 Hz
440 V AC
= 1.5 kA
cf
300 A
s per channel
2
128 A
s per channel
2
230 V ˜ 50 Hz
Terminals for 16 mm
3.5 mm pitch terminal blocks
TT or TN-C-S
W
44 k
0 V fully off, +10 V fully on
10 A or 2.3 kVA @ 230 V AC
Terminals for 3.5mm copper cable
9.2 kVA @ 230V AC
F10A HBC to IEC127
F128GD
16 Amp 600 Volt isolated tab.
BTA16 600BW
F950AJ
Page 10