Download Print this page

United Technologies Carrier BNC009 Series Installation, Start-Up And Service Instructions Manual page 9

Duct free systems

Advertisement

Fig. 12A m Legs Mounting
Base and Wiring
Outdoor
Units
Model 38BNC/BNQ009
INDOOR
UNIT 009,012,018
Operation
push button for
automatic
operation
(23°C/73°F),
turning the a/c OFF, canceling
the malfunction
indication,
and resetting the filter LED.
PLASTIC CONTROL
.....
COVER
<_
FLARING AND CONNECTING REFRIGERANT
LINES
1. Remove the protective cap from the flare fitting.
2. Remove the protective cap from the robing and cut to the
required length. Be sure that the cut is perpendicular and
clean, without burrs.
3. Slip the flare nut on the tubing and flare the tube end using
standard flaring tools.
4. Tighten the nut until resistance is met. Mark the nut and the
fitting. Using a suitable wrench tighten an additional 1/4
turn. Use the tbtlowing specified torque, according to
connection
size:
Mixed-Phase
line:
1/4 in.-(12.3
ft-lb.)
3/8 in.-(29
ft-lb.)
Suction
line:
1/2 in.-(36 ft-lb.)
5/8 in.-(47 ft-lb.)
Both
refrigerant
lines
need to be insulated
separatly
NOTE: The service valves on the outdoor unit must remain closed
until all 4 connections have been made.
EVACUATE TUBINGAND
CHARGE THE SYSTEM
When
all the fittings are connected, air must be expelled, then refriger-
ant charge must be checked and adjusted. Follow the steps below.
1. Open the service port cap on the suction line valve (laNe
valve).
SERVICE LED
3.
4.
5.
6.
7.
IR
RECEIVER
FILTER
Fig. 12B m Indoor
unit LED's
and Wiring
Connect the vacuum pump to the service port via the pressure
gage and evacuate to 500 microns to eliminate contamination
and moisture.
Disconnect the vacuum pump. Unit should maintain 500
microns for 5 minutes.
Remove the service port caps from the mixed-phase valve
and suction line valve
Open the mixed-phase valve (small valve) with an Allen
wrench.
Open the suction line valve (large valve) with an Allen
wrench.
The outdoor unit is supplied with sufficient R-22 refriger-
ant for up to 25 ft. lineset length. Add 0.9 oz. of refriger-
ant for each additional 3 ft. of tubing length.
Make sure that the valves are properly opened. Be careful not
to open them more than required as this may damage the
thread.
Replace the service port cap. Using refrigerant oil, lubricate
the cap beam and hand tighten until resistance is met. Use a
suitable wrench to tighten the cap by an additional 1/2 turn.
Power Supply
See Tables 4 and 5 tbr electrical data and Fig.
13-18 for system wiring dia_ams.
Leak Test
Leak test all fittings with appropriate test equip-
ment.

Advertisement

loading