United Technologies Carrier BNC009 Series Installation, Start-Up And Service Instructions Manual page 10

Duct free systems

Advertisement

Table 4 m Electrical
Data, Indoor Units m 30VDC
UNIT
VOLTAGE
MCA*
MOCP*
FULL LOAD
FANMOTOR COMPRESSOR COMPRESSORLOCKED
AMPS
AMPS
AMPS
ROTORAMPS
009
30VDC
N/A
N/A
1.8
1.1
N/A
N/A
40BNC
012
30VDC
N/A
N/A
1.8
1.5
N/A
N/A
40BNQ
018
30VDC
N/A
N/A
2.4
0.84
N/A
N/A
LEGEND
MCA
--Minimum
CircuitAmps
MOCP -- Maximum Overcurrent Protection
*If indoor unit is powered from outdoor terminal block, the MOCP for
the outdoor unit is for both sections
NOTE: Specifications and performance data are subject to change without notice.
3095897
Table 5 -- Electrical Data, Outdoor Units -- 115, 208/230-1-60
UNIT
VOLTAGE
MCA*
MOCP*
FULL LOAD
FANMOTOR
COMPRESSOR COMPRESSORLOCKED
AMPS
AMPS
AMPS
ROTORAMPS
009
115VAC
9.0
15
9.7
0.90
6.1
42
38BNC
012
115VAC
11.6
20
13.7
1.00
7.6
58
38BNQ
018
208-230VAC 10.7
20
10.0
0.88
6.5
42
LEGEND
MCA
--Minimum
CircuitAmps
MOCP -- Maximum Overcurrent Protection
*If indoor unit is powered from outdoor terminal block, the MOCP
for the outdoor unit is for both sections
NOTE: Specifications and performance data are subject to change without notice.
3095897