Sinclair KNX-02 Installation & Owner's Manual page 8

For sdv5 full dc inverter systems

Advertisement

2. Prepare the following assemblies on the site.
No.
Name
9
1
2-core shielded cable
10
2
86 Electrician box
Wiring Tube(Insulating
3
Sleeve and Tightening
Screw)
4
KNX power module
5
Communicate module
Note to installation of KNX:
1. One KNX module can only connect with one indoor unit;The KNX module should
connect to indoor D1D2E ports.
2. Circuit of KNX is low voltage circuit. Never connect it with a standard
220V/380V circuit or put it into a same Wiring Tube with the circuit.
3. Do not attempt to extend the shield cable by cutting, if it is necessary, use
Terminal Connection Block to connect.
4. After finishing connection, do not use Megger to have the insulation check to the
signal wire.
5. The default physical address of the KNX is 15.15.255, if there are two or more
KNX modules, then the physical addresses can not repeat.The physical address
can be changed by ETS software.
Qty.(embeded
(only for reference)
into wall)
1
RVVP-0.5mm
1
1
1
1
4
Specification
x2
2
Remarks
Max 350m