Download Print this page

Sinclair KNX-02 Installation & Owner's Manual page 14

For sdv5 full dc inverter systems

Advertisement

6: Set Auxiliary Heater ON/OFF; Data type: DPT_1.001 Switch.
Set value: 0-Auxiliary Heater OFF 1-Auxiliary Heater ON.
This function is only available for heat mode.
7: Set Heat temp;database type: DPT_9.001 temperature(°C).;
8: Mode status read; data type: DPT_20.102 HVAC mode
Read value: 0-OFF.1-Fan ; 2-Cool ; 3-Heat ; 4-Auto;5-Dry.
9: Set temperature read; data type: DPT_9.001 temperature(°C) .
10: Fan speed read; data type: DPT_20.111 FanMode
Read value: 1-speed1; 2-speed2; 3-speed3; 4-speed4; 5-speed5; 6-speed6;
7-speed7; 8-Auto
11: Fan swing status read; data type: DPT_1.001 Switch.
Read value: 0-swing OFF,1-swing ON
12:Auxiliary Heater status read; data type: DPT_1.001 Switch.
Read value: 0-Auxiliary Heater OFF,1-Auxiliary Heater ON
13:Indoor unit ambient temp. read; data type: DPT_9.001 temperature(°C)
14:Alarm state read; data type: DPT_1.005 alarm
Read value: 0-no alarm; 1-alarm
15:Set Hear temperature read; data type: DPT_9.001 temperature(°C) .
16 ON/OFF status; data type: DPT_1.001 switch
Read value: 0-OFF, 1-ON
17:ON/OFF; data type: DPT_1.001 switch
Set value: 0-OFF; 1-ON
18:Set auto mode; data type: DPT_1.001 switch
Set value: 1-set as auto mode
19:set Cool mode; data type: DPT_1.001 switch
Set value: 1-set as Cool mode
20:Set Heat mode; data type: DPT_1.001 switch
Set value: 1-set as Heat mode
10

Advertisement

loading