Download Print this page

Sinclair KNX-02 Installation & Owner's Manual page 13

For sdv5 full dc inverter systems

Advertisement

The instruction as follow:
1: set mode; database type: DPT_20.102 HVAC Mode;
set value:0-OFF ; 1-Fan only; 2-Cool; 3-Heat ; 4-Auto; 5-Dry
2: set temp; database type: DPT_9.001 temperature(°C).
The indoor unit temperature value corresponding to ETS temperature value:
No.
Temp. value(℃)
1
17
2
18
3
19
4
20
5
21
6
22
7
23
3: Set Fan speed; data type: DPT_20.111 FanMode
Set value:1-speed1; 2-speed2; 3-speed3; 4-speed4; 5-speed5; 6-speed6;
7-speed7; 8-Auto
4: Set Heat/Cool mode data type: DPT_1.100 heating/cooling.
Set value: 0-Cool mode;1-Heat mode.
5: Set swing on/off; data type: DPT_1.001 Switch.
Set value: 0-Swing off;1-Swing on.
ETS value
No.
8
0B 52
9
0B 84
10
0B B6
11
0B E8
12
0C 1A
13
0C 4C
14
0C 7E
9
Temp. value(℃)
24
25
26
27
28
29
30
ETS value
0C B0
0C E2
0D 14
0D 46
0D 78
0D AA
0D DC