Download Print this page

Electrical Connections - CDVI VIRA20245048 Manual

Firedoor electromagnetic door retainers
Hide thumbs Also See for VIRA20245048:

Advertisement

Available languages

Available languages

EN

4] ELECTRICAL CONNECTIONS

5] INSTALLATION
General instructions:
VIRA RANGE
- The door retaining magnet must be mounted on the wall or floor.
- The armature plate is mounted on the door leaf. Ensure both parts are aligned correctly.
- The door must have a reliable door closer.
- Install the magnet and armature.
- Connect the power to the magnet and verify that the magnet holds the armature plate/door securely.
- Remove the power, or push the red test button, to ensure the magnet releases the armature, and allows
the door to freely close via the door closer.
- The power to apply to release the door from the door holder has to be minimum 40 Nm
in case of switch-off button visible and accessible, whatever the force applied by the door closer,
in accordance with EN1155 regulation. In case of non-accessible switch-off button or non-existing one, the
power to apply to release the door from the door holder, whatever the force applied by the door closer,
must be between 40 and 120Nm, in accordance with the EN1155 regulation.
- Depending an the position of the electromagnetic retainer the opening angle can be lower the 90°.
Firedoor Electromagnetic door retainers
Electromagnetic
door retainer
VIRA - VIRP
Red Push
button NC
varistor
Input Voltage
24 or 48 Vdc
VIRP RANGE
7