FEATURES - ICOMFORT WI-FI® FLEX THERMOSTAT
INSTALLER SETTINGS
ADJUST SYSTEM DEVICES SCREEN (Continued)
Furnace
• Equipment Name (Keyboard tool)
• Continuous Indoor Blower Airflow (250 to 1150 cfm,
default is 315 cfm)
• Dehumidification Airflow % (60 to 80%, default is 70%)
• Delay Settings
• Heating Indoor Blower OFF
(60 to 180 sec., default is dependent on DIP switch
setting in furnace)
• Heating Indoor Blower ON
(15 to 45 sec., default is 30 sec.)
• Cooling Indoor Blower OFF
(0 to 30 sec., default is 0 sec.)
• Cooling Indoor Blower ON
(0 to 10 sec., default is 2 sec.)
• HP Indoor Blower OFF
(0 to 60 sec., default is 45 sec.)
• HP Indoor Blower ON
(0 to 30 sec., default is 0 sec.)
• Heating Airflow Control Type - Selections available if
Discharge Air Temperature Sensor is installed (Fixed
cfm, fixed Discharge Air Temperature)
With Discharge Air Temperature:
• Low Heating Discharge Air Temperature - Available
if Discharge Air Temperature Sensor is installed
(110 to 140°F, default is 125°F)
• High Heating Discharge Air Temperature - Available
if Discharge Air Temperature Sensor is installed
(120 to 150°F, default is 135°F)
With Fixed cfm:
• Low Heating Airflow
(325 to 475 cfm, default is 475 cfm)
• High Heating Airflow
(800 to 1100 cfm, default is 975 cfm)
• High Cooling Airflow
(270 to 1150 cfm, default is 825 cfm)
• High HP Airflow (300 to 1400 cfm, default is 800 cfm)
All furnace default airflow settings are dependent on
furnace capacity.
NOTE - Humidification and Dehumidification Airflow
settings are only viewable if those products are added
during setup.
Air Handler
• Equipment Name (Keyboard tool)
• Electric Heating Airflow
• High Cooling Airflow
• High HP Airflow
• Continuous Indoor Blower Airflow (450 to 1150 cfm,
default is 600 cfm)
• Humidification Airflow (Humidifier)
• Dehumidification Airflow (Dehumidifier)
(60 to 80%, default is 70%)
Dehumidification Airflow is 60 to 80% reduction of the
High Cooling Airflow parameter.
• Delay Settings
• Heating Indoor Blower OFF
(0 to 10 sec., default is 10 sec.)
• Heating Indoor Blower ON
(0 to 5 sec., default is 0 sec.)
• Cooling Indoor Blower OFF
(0 to 30 sec., default is 0 sec.)
• Cooling Indoor Blower ON
(0 to 10 sec., default is 2 sec.)
• HP Indoor Blower OFF
(0 to 60 sec., default is 45 sec.)
• HP Indoor Blower ON
(0 to 30 sec., default is 0 sec.)
Thermostat
• Equipment Name
• Temp. Reading Calibration (-5 to 5°F, default is 0°F)
• Humidity Reading Calibration (-10 to 10°F, default is 0°F)
iComfort Wi-Fi
Flex Thermostat / Page 17
®